INSTALLATION MANUAL
5.5 Commissioning
Caution!
Operate the drive in manual mode at first; not in automatic mode.
After the motor gearbox has been installed, connected and adjusted, a test run in the system is necessary. Pay
attention to the following points during the test run:
1. Ensure that no people or objects are within the working area of the motor gearbox and connected parts;
2. Check whether the vent plug is fitted in the correct position (see Section 4.1);
3. Check the operation of the system in manual mode. The direction of movement must match the indication on
the control panel;
4. Check that the limit switches and stop positions are properly adjusted, and re-adjust them if necessary (see
Section 4.5).
Tip
Install an operating hours counter.
6. Use
6.1 Noise level
The noise level (sound pressure level) at a distance of one metre is below 60 dB(A).
6.2 Heating
• The motor gearbox is not suitable for continuous operation.
• The motor gearboxes are suitable for S3-30% operation;
• The maximum continuous on time is 25 minutes;
• The motor gearbox may be cycled at most three times per minute.
Warning! Risk of burns!
The outside of the drive unit can reach temperatures in excess of 60°C.
We recommend fitting a protective cover if the unit is within easy reach.
7. Inspection and maintenance
Inspection and maintenance tasks may only be carried out by qualified staff (see Section 1.3).
7.1 Maintenance intervals
Risk of injury or death! Risk of injury or death due to electrical or mechanical forces!
Before starting to work on the motor gearbox or related parts, always switch the power off at the master
switch or operating switch and lock it out with a padlock to prevent switching on again.
Every 6 months
• Check for increased noise level
• Lubricate chain couplings (oil viscosity 80 cST to 120 cST at 20°C)
Every year
• Check and re-tighten mounting bolts
• Check couplings for wear and corrosion
• Check the limit and emergency switch mechanism for corrosion
• Re-tighten set screws in switch mechanism
• Check the wiring of the motor and the limit and emergency switch mechanism
• Check the play of the output shaft
Commissioning