The voltage is too high or
too low
Compressor stopped
because of built in
thermostat
Examine the voltage and ensure it is within
the recommended range
Discharge pressure is too
high
Examine the discharge pressure and correct
The refrigerant in the
system is not enough
Examine whether there is fluorine leakage
and repair
Filter clogging
Compressor stopped
b e c a u s e o f l o w
voltage production
Examine and change dry filter
Expansion valve failure
Adjust or change expansion valve
The refrigerant is not
enough
Fill in refrigerant
There is liquid hammer for
liquid refrigerant flowing
through evaporator to
compressor
High noise from the
compressor
Adjust liquid supply, examine whether
normal for the expansion valve and air
suction.
Over current relay is
tripped
Compressor can not
start
Set the control circuit in manual mode and
restart the compressor
The control circuit is not
connected
Examine control system
The pressure is too low,
which can not conduct the
pressure switch
No current flow
Examine power supply
The contactor coil is burnt
out
Examine whether the refrigerant is less and
refill
Water system failure, relay
is tripped
Reconnect and adjust the wiring