Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP
,
UP
and
DOWN
at the same time on the main screen of the panel.
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button
SETUP
for 4
seconds in the main screen of the panel.
Language
0 ITA / 1 ENG/ 2 FRA / 3 ESP
COS-PHI Alarm Output
This parameter enables removal of the dry running alarm from the
cumulative alarm output.
Sensor Sensitivity (Sa - Sb - Sc - Sd)
This parameter enables display of sensor sensitivity. With the contacts open, if
a value of 99 is displayed, and a value of 45 is displayed with water present,
s e t s e n s i t i v i t y t o a n i n t e r m e d i a t e v a l u e , s u c h a s 7 5 .
DESCRIPTION OF PARAMETER
VALUE
Operating Logic
0
FAULT
0
8
-
Y or N
0-99
Y
75
Minimum Voltage
Set by default at -10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
Maximum Voltage
Set by default at +10% .
Modifications to operating limits beyond the default parameters will
i m m e d i a t e l y r e n d e r t h e w a r r a n t y n u l l a n d v o i d .
DESCRIPTION OF PARAMETER
VALUE
207 (230)
FAULT
360 (400)
-
-
253 (230)
440 (400)
Alarm Float Switch
Motor Clicson
Start Float/ Pressure Switch
Min Level Input
Cumulative Alarm Output
Earthing Grounding
Motor Output
Starting Capacitor
(1-phase)
Supply Input
(T for 3-phase)