Day and Night CCH6 Скачать руководство пользователя страница 9

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

428 01 1703 01

9

Specifications subject to change without notice.

Unit is factory charged for 15ft  (4.57 m) of lineset. Adjust

charge by adding or removing 0.6 oz/ft of 3/8 liquid line

above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less),

allow system to operate in cooling mode at least 15 minutes.

When operating with the Observer Wall Control in

communicating mode make sure that indoor airflow is set to

the final operating selection (Eff 325, Eff 350, Comfort,

Maximum) during charging. If conditions are favorable, check

system charge by subcooling method. If any adjustment is

necessary, adjust charge slowly and allow system to operate

for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

F (26.67

C), and the

outdoor temperature is in the favorable range, adjust system

charge by weight based on line length and allow the indoor

temperature to drop to 80

F (26.67

C) before attempting to

check system charge by subcooling method as described

above.
If the indoor temperature is below 70

F (21.11

C), or the

outdoor temperature is not in the favorable range, adjust

charge for line set length above or below 15ft (4.57 m) only.

Charge level should then be appropriate for the system to

achieve rated capacity. The charge level could then be

checked at another time when the both indoor and outdoor

temperatures are in a more favorable range.

NOTE

: The Observer Wall Control has a staging timer, to

override the staging timer for charging in high

stage create

at least a 5 degree difference between room and set point

temperatures and hold the “Cool To” button for 10 seconds
on the thermostat home screen.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than

20 ft (6.10 m) vertical separation,  See Long Line Applications

Guideline for special charging requirements.

Heating Tech Label

To check system operation during heating cycle, refer to the

Heating Tech Label on outdoor unit. This label indicates

whether a correct relationship exists between system

operating pressure and air temperature entering indoor and

outdoor units. If pressure and temperature do not match on

chart, system refrigerant charge may not be correct. Do not

use label to adjust refrigerant charge.

SYSTEM FUNCTIONS AND SEQUENCE OF

OPERATION

The *CH9 and *CH6 models utilize either an Observer

Communicating Wall Control or a 2-stage cooling thermostat.

With a call for first stage cooling, the outdoor fan and

low-stage compressor are energized. If low-stage cannot

satisfy cooling demand, high-stage is energized by the

second stage of the indoor thermostat. After second stage is

satisfied, the unit returns to low-stage operation until first

stage is satisfied or until second stage is required again.

When both first stage and second stage cooling are satisfied,

the compressor will shut off. When a 2-stage unit is operating

at low-stage, system vapor (suction) pressure will be higher

than a standard single-stage system or high-stage operation.

When the outdoor ambient is more than 100

F (37.8

C), the

outdoor fan will continue to run for one minute after

compressor shuts off, this reduces pressure differential for

easier starting in the next cycle.
With non-communicating (non-Observer) systems, with first

stage of cooling, Y1 and O are powered on; and with second

stage of cooling, Y1, Y2, and O are on. For these systems,

with first stage of heating Y1 is on and for second stage of

heating, Y1 and Y2 are on. When the reversing valve is

energized, O is powered on.

Communication and Status Function Lights

Green communications (COMM) Light (Only with

Observer Communicating Wall Control)

A green LED (COMM light) on the outdoor board indicates

successful communication with the other system products.

The green LED will remain OFF until communications is

established. Once a valid command is received, the green

LED will turn ON continuously. If no communication is

received within 2 minutes, the LED will be turned OFF until

the next valid communication.

Amber Status Light (STATUS)

An amber colored STATUS light is used to display the

operation mode and fault codes as specified in the

troubleshooting section.  See Table 3 for codes and

definitions.

NOTE

: Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority).

Utility Interface with Non-Communicating

Thermostat

The utility curtailment relay should be wired in the Y2

thermostat lead.  This allows a power utility device to interrupt

high stage compressor operation during peak load periods. If

the utility requires control of low stage compressor operation

a second utility curtailment relay should be wired in the Y1

lead.

NOTE

: Utility curtailment is not available when operating in

communicating mode.  To apply utility curtailment with the
Observer Wall Control you must use a daughter board kit to

convert the control signals to standard thermostat signals.

Compressor Operation

The basic scroll design has been modified with the addition

of an internal unloading mechanism that opens a by-pass

port in the first compression pocket, effectively reducing the

displacement of the scroll.  The opening and closing of the

by-pass port is controlled by an  internal electrically operated

solenoid. The modulated scroll uses a single step of

unloading to go from full capacity to approximately 67%

capacity. 

A single speed, high efficiency motor continues to run while

the scroll modulates between the two capacity steps.

Modulation is achieved by venting a portion of the gas in the

first suction pocket back to the low side of the compressor,

thereby reducing the effective displacement of the

compressor. 

Full capacity is achieved by blocking these vents, thus

increasing the displacement to 100%.  A DC solenoid in the

compressor controlled by a rectified 24 volt AC signal in the

external solenoid plug moves the slider ring that covers and

uncovers these vents. The vent covers are arranged in such

a manner that the compressor operates at approximately

67% capacity when the solenoid is not energized and 100%

capacity when the solenoid is energized. The loading and

unloading of the two step scroll is done “on the fly” without

shutting off the motor between steps.

NOTE

: 67% compressor capacity translates to approximately

75% cooling capacity at the indoor coil. The compressor will
always start unloaded and stay unloaded for five seconds even
when the thermostat is calling for high

stage capacity.

Crankcase Heater Operation

The crankcase heater is de-energized when the compressor

is running.  The crankcase heater is energized when the

compressor is off and the ambient is less than 42

 F.  When

the ambient temperature is between 65

 F and 42

 F the

crankcase heater is energized 30 minutes after the

compressor is turned off.  When the ambient is above 65

 F

Содержание CCH6

Страница 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Страница 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Страница 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Страница 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Страница 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Страница 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Страница 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Страница 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Страница 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Страница 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Страница 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Страница 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Страница 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Страница 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Страница 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Страница 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Отзывы: