No.
Phenomena
Reason
Solutions
1
Cannot read modbus
No power supply, the
power cord is incorrectly
connected;
Modbus connection pin A, B
is loose or wrong;
Configuration slave
address, baudrate, parity is
not correct;
Reading the wrong
command, wrong address
register.
Check the power
connection;
Check the connection
modbus A, B;
Check the configuration of
slave address, baudrate,
parity;
The product only supports
modbus 3, 4, and 16.
Check if the value of
modbus status returned by
2 or 3 is an incorrect
address reading.
2
Cannot add slave into master
No power supply, the
power cord is incorrectly
connected;
The antenna is not
fastened or connected;
Slave registered with
another Master.
Reset Slave with push
button or magnet;
Check the power
connection;
Disconnect the power
source and reattach, then
proceed to add
automatically.