Step 6: Write the new setting to parameter with function 16
Double click on column Setting Value of the parameter and input new setting of the parameter
Uncheck the tick on Func column of the parameter, click on the arrow, select 16 and then check on the Func
column to write new setting to the parameter. The OK text will show on Read Column if the software successfully
writes the setting.
Repeat the step 5 to read the setting of the parameter for checking.
No.
Phenomena
Reason
Solutions
1
Status on the software always
shows Disconnected although
the configuration cable is
connected to the PC
The selected COM port is
incorrect.
The cable is defective
Select the correct COM port to
which the configuration cable
connects to PC
Check the cable
For some critical parameters of the sensor, the password in "password for setting" must be written before
writing the new settings to these parameters.
Only read/write registers are allowed to write
4. Troubleshooting