IP
Static IP configuration for iConnector. Example: 192.168.1.30
Gateway
Configure gateway
DNS Server
Configure DNS Server
DHCP
0 (Off) / 1 (On)
If DHCP = 0, it's mean Not using DHCP → Static IP
Name
Description
Modbus-TCP Port
Configure the receiving port, for example 502
Modbus-TCP enb transparent
1 : To run transparent, interrupt modbus RTU poll.
0 : Run modbus RTU poll as normal iConnector, not transparent
Modbus-TCP timeout (ms)
Used for modbus TCP Server
Suppose we have: Static IP address: 192.168.1.30 | Port 502
1. iConnector is connected to the Modbus RTU with electric meters, devices, ... via RS485 port;
2. Software / device / PLC ... with Modbus TCP Client connected to iConnector (role as TCP Server) at Static IP
address 192.168.1.30 | Port 502 in internal network;
3. TCP Client sends command to iConnector;
4. iConnector transfers commands from Modbus TCP to RTU and sends to devices and clocks via RS485 port;
5. iConnector waits for the devices to respond;
6. iConnector transfers the response from the RTU to the Modbus TCP and then sends it back to the TCP Client;
7. TCP Client actively closes the connection if it no longer sends command to iConnector.
1. iConnector needs static IP configuration, For example: IP 192.168.1.30 | Port 502
3.3.2.2 Modbus-TCP-Server tab
2.3.3 Description of transparent mode operation
(Modbus-TCP enb transparent = 1)
2.3.4 Run Modbus RTU as normal iConnector
(Modbus-TCP enb transparent = 0)
3.3.4.1 TCP Client connects to iConnector via internet
Содержание iConnector STHC
Страница 18: ...END...
Страница 21: ......
Страница 25: ...VI How to add iConnector STHC to Globiots Server System...
Страница 26: ...VII Modbus Configuration for iConnector STHC on Globiots...
Страница 27: ...VIII Parameter Configuration for iConnector STHC on Globiots...
Страница 28: ...IX Alarm Event Configuration for iConnector STHC on Glbiots...
Страница 29: ...X Configuring special functions of iConnector on Globiots...