background image

6

PRESSURE SWITCH

Your Davey RVM pump set should have the correct pressure switch setting for zero 

suction lift. If your pump is installed on a suction lift you may need to adjust the 

pressure setting to suit.

Any adjustment of the pressure switch settings should be made according to the pump 

curve*. The cut-out pressure should never be higher than 90% of the maximum pump 

shut head pressure OR higher than the maximum operating pressure for the pressure 

tank and the cut-in pressure should be set within the pump curve*. 

XMP12 Adjustments

To adjust the 

cut-out (high) pressure

 of the system, 

turn the large dial (1) to the desired direction: + (CW) 

for higher pressure, – (ACW) for lower pressure.
To adjust the 

cut-in (low) pressure

 of the system, turn 

the smaller screw (2) to the desired direction: + (ACW) 

for higher pressure, – (CW) for lower pressure.

9013GHG2 Adjustments

Cut-in Adjustment (range):

 Always adjust the cut-in 

spring nut (A) first, setting it to the desired operating 

point. Keep in mind that adjustment changes both the 

high and low operating points, but it should always be adjusted for the cut-in (low) operating point. Turning the nut (A) 

clockwise increases the setting.

Cut-out Adjustment (differential):

 to set the cut-out operating point, adjust the differential spring nut (B). Turning the nut 

(B) clockwise increases the cut-out (high) operating point, which effectively increases the pressure difference between the 

high and low operating points.

TANK PRECHARGE

The pressure tank fitted to your Davey pump set should be pre-charged with air to a value of 15kPa below the cut in 

pressure. Refer to the table in the maintenance section of these instructions.

CHOOSING A SITE

Choose a site with a firm base and as close to the water source as possible with correct power supply. Make sure your 

pressure pump is always connected to an adequate, reliable source of clean water.

Housing your Davey Pump:

 To protect your pump from the weather, make sure the housing is both water proof, frost 

free and has adequate ventilation.

The pump set should be mounted on its base in a firm dry area allowing for drainage, to avoid damage due to flooding 

etc., that over time may occur from leaking pipe joints or pump seals.

POWER CONNECTION

Only connect the pump set to the power supply designated on the pump and motor label.

Single-phase pumps up to 1.5kW have a built in thermal overloads and have been provided with a 10 amp cable and plug 

for connection to a standard power outlet.

Single-phase 2.2kW pumps have a built in thermal overload and have been provided with a 15 amp cable and plug for 

connection to a standard 15 amp power outlet. 

Do not use long extension leads as they cause substantial voltage drop, poor pump performance and may cause motor 

overload.

Larger single phase and three phase pump sets should be wired to an approved overload by a licensed and qualified 

electrician.

ELECTRICAL POWER SURGE PROTECTION

An electrical power surge or spike can travel along the supply lines and cause serious damage to your electrical 

equipment. The RVM controller fitted to this system has a metal oxide varistor (MOV) fitted to help protect its circuit. 

This MOV is a “sacrificial” device, meaning that it is gradually damaged every time it takes a surge. The MOV is not a 

lightning arrestor and may not protect the control unit if lightning or a very powerful surge hits the pump unit.

B

A

WARNING: Some insects, such as small ants, find electrical devices attractive for various reasons.  

If your pump enclosure is susceptible to insect infestation you should implement a suitable pest 

control plan.

The electrical connections and checks must be made by a qualified electrician and comply with 

applicable local standards.

* Adjusted for site conditions, i.e. suction life or positive suction pressure

Содержание RVM Series

Страница 1: ...ation remove the inlet and outlet pipe transport plugs associated seals from the suction and or discharge ports WARNING The RVM system and associated pipework operate under pressure Under no circumsta...

Страница 2: ...troller 415V Connection Diagram 15 Manual Automatic Start Controller 240V Connection Diagram 16 Manual Automatic Start Controller 415V Connection Diagram 17 TROUBLE SHOOTING CHECK LIST 18 TERMS AND CO...

Страница 3: ...o handle clean clear water It should not be used for any other purpose without specific referral to Davey The use of the pump to handle flammable corrosive and other materials of a hazardous nature is...

Страница 4: ...e plate 3 Check valve 4 Discharge manifold 5 Pressure gauge Not shown 6 Pressure switches 7 Isolation valve 8 Flow switches 9 Pressure tank 10 RVM water pressure system control box RVM Water Pressure...

Страница 5: ...old 5 Isolation valve 6 Flow switches 7 RVM water pressure system control box RVM REMOTE START SYSTEM WITH LOSS OF PRIME CONTROL BOX RVM MANUAL AUTOMATIC START SYSTEM WITH LOSS OF PRIME CONTROL BOX co...

Страница 6: ...pump is always connected to an adequate reliable source of clean water Housing your Davey Pump To protect your pump from the weather make sure the housing is both water proof frost free and has adequ...

Страница 7: ...er Supply to either Suction or Discharge of Pump Most Water Supply Authorities have strict regulations regarding direct connection of pumps to mains water supplies In most cases an isolating storage t...

Страница 8: ...100RHP HP24 300 650 285 VM5 8 1 5 100RHP HP24 300 700 285 VM5 10 2 2 100RHP HP24 450 950 435 VM5 12 3 HP24 500 1100 485 VM5 14 3 HP24 600 1300 585 VM5 16 3 HP24 650 1500 635 VM10 4 1 5 100R HP24 300...

Страница 9: ...a the pressure and flow switches OFF The pump will not operate in this mode MANUAL The pump operates manually for 2 minutes then switches to AUTO mode FAULT RESET Pressing this button resets all alarm...

Страница 10: ...switches OFF The pump will not operate in this mode MANUAL The pump operates manually for 2 minutes then switches to AUTO mode FAULT RESET Pressing this button resets all alarms FAULT RESET Pressing...

Страница 11: ...ches OFF The pump will not operate in this mode MANUAL The pump operates manually for 2 minutes then switches to AUTO mode FAULT RESET Pressing this button resets all alarms FAULT RESET Pressing this...

Страница 12: ...ntrol boxes Pressure Start Controller 240V IF PUMP HAS CAPACITOR FITTED IN THE LEAD INSTALL HERE ALARM CONTACT 240VAC 10 AMPS N C COM N O PUMP 1 240VAC PRESSURE SWITCH SUPPLY 240 VAC FLOW SWITCH L N C...

Страница 13: ...13 Pressure Start Controller 415V ALARM CONTACT 240VAC 10 AMPS N C COM N O 415VAC PRESSURE SWITCH SUPPLY 415 VAC FLOW SWITCH L1 L2 L3 N PUMP 1 PUMP 1 CONTACTOR RVM...

Страница 14: ...N 240VAC PUMP 1 IF PUMP HAS CAPACITOR FITTED IN THE LEAD INSTALL HERE C SCREAM SCR SCR N O COM N C HLA HLA START START OVLD OVLD ALARM OVLD START HLA ALARM CONTACT 240VAC 10 AMPS RATED PCB 18 17 15 16...

Страница 15: ...1 2 3 4 5 T1 T2 T3 L2 L3 PUMP 1 CONTACTOR 415VAC PUMP 1 6 SCREAM SCR SCR N O COM N C HLA HLA START START OVLD OVLD ALARM OVLD START HLA ALARM CONTACT 240VAC 10 AMPS RATED PCB 18 17 15 16 FLOW SWITCH...

Страница 16: ...PUMP 1 IF PUMP HAS CAPACITOR FITTED IN THE LEAD INSTALL HERE C SCREAM SCR SCR N O COM N C HLA HLA START START OVLD OVLD ALARM OVLD START HLA ALARM CONTACT 240VAC 10 AMPS RATED PCB 18 17 15 16 FLOW SW...

Страница 17: ...4 5 T1 T2 T3 L2 L3 PUMP 1 CONTACTOR 415VAC PUMP 1 6 SCREAM SCR SCR N O COM N C HLA HLA START START OVLD OVLD ALARM OVLD START HLA ALARM CONTACT 240VAC 10 AMPS RATED PCB 18 17 15 16 FLOW SWITCH N C COM...

Страница 18: ...s up to 2 2kW are fitted with an automatic over temperature cut out Constant tripping of this overload device indicates a problem e g low voltage at pump excessive temperature above 40 C in pump enclo...

Страница 19: ...NOTES...

Страница 20: ...receipt as proof of purchase you MUST provide evidence of the date of original purchase when claiming under the Davey Two Year Guarantee Davey shall not be liable for any loss of profits or any conse...

Отзывы: