Example for the practical usage of the limit outputs
Task:
The limit output No.1 should control a heater, that switches
ON when the temperature goes lower than 70 °C, and
switches OFF when it goes higher than 90 °C.
The limit output No.2 should control a buzzer. The buzzer
should be signalling continuously as long as a manual
acknowledgement takes place, in those cases when the
temperature goes, at any time, lower than 50 °C, or when it
goes higher than 95 °C
The settings of the limit outputs are as follows:
operating mode=
(Switches ON, when the
temperature is lower than the low limit)
Low limit =
°C
Hysteresis of the low limit =
°C
High limit =
°C (it’s value is indifferent)
Hysteresis of the high limit =
°C (it’s value is
indifferent)
Alarm mode =
Operating mode=
(Switches ON, when the
temperature does not fall between the limits.)
Low limit =
°C
Hysteresis of the low limit =
°C
High limit =
°C
Hysteresis of the high limit =
°C
Alarm mode =
Содержание DT9502
Страница 1: ...DT9502 Intrinsically Safe Temperature Meter Transmitter Operating Instructions ...
Страница 64: ...DT9502 64 20171205 V3 10 2 Application example ...
Страница 84: ...DT9502 84 20171205 V3 10 9 ATEX Certification ...
Страница 85: ...DT9502 20171205 V3 85 ...
Страница 86: ...DT9502 86 20171205 V3 ...
Страница 87: ...DT9502 20171205 V3 87 ...
Страница 88: ...DT9502 88 20171205 V3 ...
Страница 89: ...DT9502 20171205 V3 89 ...
Страница 90: ...DT9502 90 20171205 V3 ...
Страница 91: ...DT9502 20171205 V3 91 ...
Страница 92: ......