Setting the operating
mode
Sequence of operations
5. Keep stepping by pressing the
▲
button you can select
the desired limit-output operating mode.
•
: the output is always in switched off condition.
[default factory setting]
•
: (
≥
L
) The output gets switched on, when the
displayed physical value is higher than or equal with the low
limit value (LL).
•
: (
<L
) The output gets switched on, when the
displayed physical value is lower than the low limit value
(LL).
•
: (
≥
L
and
≤
H
) The output gets switched on, when
the displayed physical value is between the low limit value
(LL) and the higher limit value (HL).
•
: (
<L
or
>H
) The output gets switched on, when
the displayed physical value isn’t between the low limit
value (LL) and the high limit value (HL).
•
: the output is always in switched on condition
Setting the operating
mode
Sequence of operations
6. After you have selected the desired operating mode for
the limit output, press the
MENU
button. This takes you out
from the given sub-menu item, and you see this:
.
7. If you had selected the
or the
mode, there is no
need to do any further settings. For finishing the operation,
please go on from the point
Exit from the menu item
.