7
4.2. Inputs with 0,5 mA current
Inputs with 0.5 mA current are available optionally to satisfy specific customer needs.
Input parameters:
Short-circuit
current:
<
0.5
mA
6%
Input
resistance: 18
k
.
5. Operating principle
.
The operation of the device is shown in the block diagram of Figure 1.
Figure 1. The theoretical build-up of the device
The comparator unit detects the current flowing over the 1 k
resistor connected serially with the +8.2 V voltage
generator. The threshold values in accordance with the NAMUR standard are as follows:
Direct switch position:
> 2.1 mA
Reverse switch position:
< 1.2 mA
Sensor line broken:
< 0.15 mA
Sensor line short:
> 6.0 mA
The following settings can be realized with the operating mode switch mounted inside the device (triple DIL-
switch):
S1, Direct – Reverse
S2, Detecting if the line is broken
S3, Detecting if the line is short
The function of detecting if the line is broken or short is applicable only when a NAMUR input detector is used!
In the case of operation with contact switch, the network in accordance with Figure 2 must be used for
establishing the connection to the contact switch ( S2 and S3 in ON position ).