DI-789 Hardware Manual
Installation
11
here. The software will go to that IP address and retrieve the MAC address for you. This will save further setup
in the TCP/IP Manager. Click
OK
to continue.
Note: If you enter the wrong MAC address you will have to re-run
this installation program with the correct MAC address to access the device.
14. Click
Yes
in the “More ethernet devices to install” dialog box if you are installing multiple Ethernet devices.
15. Repeat Steps 12 and 13 until all Ethernet devices’ MAC addresses have been entered. Click
No
to continue
installation.
16. The “Installation Option” dialog box allows you to specify access to W
IN
D
AQ
for multiple users on the same PC.
If you are the only user or you would like to allow access to all users click
Yes
. If there are multiple users and
you would like to be the only one able to access W
IN
D
AQ
click
No
. Click
Cancel
to abort the installation.
17. Select the desired options for installation of W
IN
D
AQ
/XL and Advanced CODAS.
18. Installation is complete. Run the TCP/IP Manager via the Windows program group specified during W
IN
D
AQ
Software installation (default is
Start > Programs > WINDAQ > IP Manager
) to access the device and run
W
IN
D
AQ
Acquisition Software.
Connecting the Device
After power has been applied, install the DI-789 anywhere in a chain of Synchronous Ethernet instruments. Multiple
Ethernet products may be daisy-chained together to allow for one synchronous distributed data acquisition system.
Any combination of multiple DI-789s or Synchronous Ethernet instruments may be placed in the same daisy chain.
To maintain synchronicity, Ethernet hubs and switches cannot be used between units. Make sure to enter each MAC
address during installation. Daisy-chains must be installed to your Local Area Network (LAN) — you cannot access
more than one device per IP address outside of your subnet. If you are not sure whether or not the devices are in your
subnet see your system administrator before installation. You may acquire data from only one daisy chain at a time
(i.e., the same PC cannot access two daisy chained groups at the same time).
Note: If you are installing a daisy-chained group of instruments for the purpose of synchronous distributed data
acquisition, do not allow any other units or daisy chains to be installed to your subnet. Running other devices on the
same subnet will cause the synced units to become unsynced.
1.
Connect one end of a CAT-5 Ethernet cable to the
Toward PC
port of the first Ethernet device.
2.
Connect the other end of the same CAT-5 Ethernet cable to the Ethernet port on your PC or LAN.
3.
Connect one end of another CAT-5 Ethernet Cable to the
Expansion
port on the rear of the first Ethernet device.
4.
Connect the other end of the same CAT-5 Ethernet cable to the
Toward PC
port on the second Ethernet device.
5.
Continue installing more Ethernet devices by connecting a CAT-5 Ethernet cable to the
Expansion
port of the
last device in the chain and the
Toward PC
port on the next device you are adding to the chain. Up to 32 devices