Serial iBootBar  v090212d 

 
 

Device Commands 

 

Command 

Description 

Access 

Fact Default 

get outlets 

This command displays a list of connected devices, and their current 
status.   

User 

 

set name <name> 

Set the name of the selected iBootBar.  20 characters max. 

User 

 

get current 

Gets the measured current of the iBootBar 

Admin

 

 

get external control  

set external control <enable/disable> 

Get or set external control capability.  Enabling this will allow the 
external inputs to control its corresponding outlet. 

Admin

 

enable 

get cycle 

set cycle <1-99> 

Get or set the cycle time in seconds. Cycle time is the time that the 
outlet will be off during a reboot (on – off – on) or on during a cycle (off 
– on – off) 

User 

10 

get delay 

set delay <0-99> 

Get or set the delay time in seconds.  When multiple outlets are 
turned On by a single command, this delay controls the interval 
between powering up of the outlets.  This delay is us ed to limit power 
up inrush. 

User 

get current alarm 

set main <a/b> highalarm <nn.n> 

set main <a/b> lowalarm <nn.n> 

High and Low alarms are used to monitor current conditions and 
send an alert via the serial port when the high or low thresholds are 
exceeded.   
From 0.0 to 10.0/15.0/20.0 (depending on max current for device) in 
0.1 amp increments.  For devices with two Mains, Main A and Main B 
are set separately, but displayed together with the get command. 

Admin

 

Highalarm:  

10.0 for 10 Amp 
Models 

15.0 for 15 Amp 
Models 

20.0 for 20 Amp 
Models 

Lowalarm: 

0.0 Amp 

Содержание sBB-2C10

Страница 1: ... via RS 232 serial communications and via contact closure inputs The following models are covered in this document Model Power Feed Total Capacity Outlets sBB N15 NEMA 15 Amp 8 x NEMA 5 15 sBB 2N15 2 x NEMA 30 Amp 8 x NEMA 5 15 sBB N20 NEMA 20 Amp 8 x NEMA 5 15 sBB 2N20 2 x NEMA 40 Amp 8 x NEMA 5 15 sBB C10 IEC C14 10 Amp 8 x IEC C13 sBB 2C10 2 x IEC C14 20 Amp 8 x IEC C13 sBB C20 IEC C20 20 Amp 8...

Страница 2: ......

Страница 3: ...y Instructions 4 Quick Start 5 General Overview 6 Installation 7 Rack Mounting Serial Port Contact Closure Inputs Power Source Serial Operation 9 Control Input Operation 14 Advanced Operation 15 Specifications 17 Compliance Statements 18 Technical Support Warranty 19 ...

Страница 4: ... the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product where the cord will be abused by persons walking on it 10 Do not overload wall outlets and extension cords as this can result in the risk of fire or ele...

Страница 5: ...et status iBootBar get outlets To turn on off outlet 1 iBootBar set outlet 1 off To reboot outlet 2 iBootBar set outlet 2 cycle Outlet Status Indicators Reset Pushbutton Recessed Mains Inlet Power Indicators Linecord for NEMA Models Circuit Breaker 2nd Linecord and Circuit Breaker on 2N Models 8 NEMA 5 15 Outlets Serial DCE Control Inputs Expansion for Future Applications 8 IEC C13 Outlets IEC C 1...

Страница 6: ... models Models with dual inputs sBB 2N or sBB 2C have two inlets mains Each main feeds four outlets Inlet A supports outlets 1 4 and Inlet B feeds 5 8 Dual power inlet models can be used to support higher current devices as each inlet can carry its rated load doubling the amperage of a single inlet device Dual Inlet models can also be used to source power from two redundant sources with each sourc...

Страница 7: ...l outlets using contact closure contact open connections Each connection marked 1 through 8 controls the outlet of the same number The remaining 8 connections are ground and are interchangeable Using a small flat blade screwdriver depress the wire release mechanism for one of the terminals on the terminal block and insert the bare wire into the terminal Remove the screwdriver to secure the wire Ge...

Страница 8: ...Page 8 Serial iBootBar v090212d Expansion Future Expansion No function in the current Serial iBootBar ...

Страница 9: ...nal applications and can be used on 100V to 240VAC The sBB 2C10 provides two IEC 320 style universal inlets for connecting a detachable power cord Two standard IEC to CEE7 European cord sets are supplied with the unit for use on 10 Amp 240VAC service The total maximum current load for outlets on any linecord cannot exceed 12 Amps at 115VAC or 10 Amps when used at 240VAC Each linecord distributes p...

Страница 10: ... must have rights to the selected outlet User set outlet 1 8 on off cycle Sets the selected outlet to the selected state The user must have rights to the selected outlet User set outlet 1 8 name name Sets the name of the selected outlet of the selected iBootBar 20 characters max Admin Outlet get outlet n control on set outlet n control on open closed Gets or sets the state that the control input c...

Страница 11: ... Add user rights to outlets and groups Admin del user username Deletes the selected user from the root iBootBar s user table Admin ren user username newname Renames the selected user in the root iBootBar s user table 20 character max Admin set user username outlet 1 8 all yes no Sets the users right to the selected outlet Admin No Rights set user username group name yes no Sets the user s rights t...

Страница 12: ...off during a reboot on off on or on during a cycle off on off User 10 get delay set delay 0 99 Get or set the delay time in seconds When multiple outlets are turned On by a single command this delay controls the interval between powering up of the outlets This delay is used to limit power up inrush User 1 get current alarm set main a b highalarm nn n set main a b lowalarm nn n High and Low alarms ...

Страница 13: ...min 120 set console baudrate 2400 4800 9600 19200 38400 57600 115200 The baud rate of the serial port 400 4800 9600 19200 38400 57600 115200 bps Admin 115200 set factory defaults Resets all parameters to their factory settings Confirmation is required Note This command can take up to 30 seconds to execute Admin logout Ends the session User reboot Reboots the selected iBootBar This will not change ...

Страница 14: ...ds or deletes a specific outlet on a specific device from the selected group Admin ren group groupname newname Renames the selected group 20 characters max Admin del group groupname Deletes the selected group Admin Firmware Upload Commands Command Description Access Fact Def get upload enable Admin set upload enable Get or set the ability for the root iBootBar to accept a firmware upload Admin No ...

Страница 15: ...ry switch or relay closures or open collector relay drivers to connect to the sBB inputs If you have any doubts about proper connections consult Dataprobe Technical support The default control is Input Open Outlet On Input Grounded Outlet Off This can be changed using the set outlet n control on open closed command Example set outlet 3 control on closed Causes Outlet three to be Input Closed to Gr...

Страница 16: ...ges will be formatted as follows cr lf device name outlet outlet name control type source cr lf Where cr ASCII carriage return lf ASCII line feed character device name User programmed name of the sBB outlet The number of the outlet 1 8 outlet name the user programmed name of the outlet that has changed source CLI Expansion Port or Control Port Example ServerRoom ServerA Off Expansion Port Alarm Me...

Страница 17: ...nload the latest version of the firmware and upgrade utility from the Dataprobe website Password Recovery Holding the reset button on the front panel of the iBootBar for 5 seconds or longer will initiate a password recovery mode Once the reset button is released the user has 30 seconds to log in to the CLI using the username admin and password admin Upon accessing the CLI change the username and p...

Страница 18: ... I S M sBB 2N20 2 x N20 8 x N15 I S sBB 2N20 M 2 x N20 8 x N15 I S M sBB C10 C14 8 x C13 I S sBB C10 M C14 8 x C13 I S M sBB 2C10 2 x C14 8 x C13 I S sBB 2C10 M 2 x C14 8 x C13 I S M sBB C20 C20 8 x C13 I S sBB C20 M C20 8 x C13 I S M sBB 2C20 2 x C20 8 x C13 I S sBB 2C20 M 2 x C20 8 x C13 I S M Key Input N15 NEMA 5 15 Linecord 115VAC 15 Amps combined total switched N20 NEMA 5 20 Linecord 115VAC 2...

Страница 19: ...lies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment EMC ...

Страница 20: ... Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN EX...

Отзывы: