iP-28xx
Page 8
Menu Operation
The menu system is the same using Telnet or via the Serial Port or Internal Modem.
Access for operation via Telnet, Serial or Modem is the same as access for configuration.
xP-2815
Location: Location Name
Outlet Status Linked Outlet Status
1. Router 1 ON Yes 5. Router 1a ON
2. Router 2 ON No 6. Router 3 OFF
3. Server 1 OFF No 7. Server 3 ON
4. Server 2 ON Yes 8. Server 2a ON
# - Select relay to toggle or A for all
C# - Cycle Outlets
L# - Link Outlets
S - Setup
X - Exit
Enter >
The screen shows the current status of all power outlets.
To change the status of any outlet, type the outlet number and <Enter> at the prompt.
If the outlets are linked, it will be shown in the Linked column. Selecting either one of the linked outlets will cause the other to
work simultaneously.
You can change all circuits simultaneously by selecting A and <Enter> for All.
To momentarily cycle the status of an outlet, for power reboot, enter C and the outlet number plus <Enter> The status will
change while the outlet is cycling. The duration of the cycle is determined in the setup. The default is 10 seconds.
All circuits can simultaneously be cycled by selecting PA <Enter>.
Outlets can be linked in pairs to provide simultaneous switching for systems with dual redundant power supplies. The
following outlets can be linked.
1 and 5
2 and 6
3 and 7
4 and 8
Each pair can be selectively linked. Enter L plus either of the outlet numbers to link or unlink the pair. The link status will be
shown as Yes or No under the Linked column for that pair.