background image

 
 
 

iBootBar 

– Precision Version 

 

   

Page 20 

iBootBar_Precision_20160428e.doc 

 

Firmware ver 1.41.32 

 

  

 

SNMP MIB 

 
Download at  dataprobe.com\ibootbartools.html 
 
enterprises [1.3.6.1.4.1] 
    | 
    ->  [1418] -MI- dataprobe 
        | 
        ->  [ 4] -BR- iBootBarAgent 
            | 
            ->  [ 1] -BR- systemSettings 
                | 
                ->  [ 1] *RW* DisplayString 

 

deviceName 

                ->  [ 2] *RW* INTEGER(Enum) 

ipMode 

                ->  [ 3] *RW* DisplayString 

 

ipAddress 

                ->  [ 4] *RW* DisplayString 

 

subnetMask 

                ->  [ 5] *RW* DisplayString 

 

gateway 

                ->  [ 6] *RW* INTEGER(Enum) 

webEnable 

                ->  [ 7] *RW* Integer32 

 

webPort 

                ->  [ 8] *RW* INTEGER(Enum) 

sslEnable 

                ->  [ 9] *RW* INTEGER(Enum) 

telnetEnable 

                ->  [10] *RW* Integer32 

 

telnetPort 

                ->  [11] *RW* INTEGER(Enum) 

updateEnable 

                ->  [12] *RW* Integer32 

 

cycleTime 

                ->  [13] *RW* Integer32 

 

delayTime 

            | 
            ->  [ 2] -TB- snmpManagerTable 
                | 
                ->  [ 1] -TE- snmpManagerEntry 
                    | 
                    ->  [ 1] *RO* Integer32 

 

snmpManagerIndex 

                    ->  [ 2] *RW* DisplayString   

snmpManagerIPAddress 

                    ->  [ 3] *RW* INTEGER(Enum) 

snmpManagerEnable 

            | 
            ->  [ 3] -TB- outletTable 
                | 
                ->  [ 1] -TE- outletEntry 
                    | 
                    ->  [ 1] *RO* Integer32 

 

outletIndex 

                    ->  [ 2] *RW* OCTET STRING 

outletName 

                    ->  [ 3] *RO* INTEGER(Enum) 

outletStatus 

                    ->  [ 4] *RW* INTEGER(Enum) 

outletCommand 

                    ->  [ 5] *RO* INTEGER(Enum) 

outletAPStatus 

            | 
            ->  [ 4] -BR- info 
                | 
                ->  [ 1] *RO* Integer32  

 

currentLC1 

                ->  [ 2] *RO* Integer32  

 

currentLC2 

                ->  [ 3] *RO* INTEGER(Enum)  

numberOfLineCords 

            | 
            ->  [ 5] -NT- outletChange 
            ->  [ 6] -NT- autoPingFailed 
            ->  [ 7] -NT- newNotifTyp01 
 

Legend : 
AC - Agent Capabilities 
AN - Accessible for Notify 
BR - Branch 
MC - Module Compliance 
MI - Module Identity 
NA - Not Accessible 
NG - Notification Group 
NT - Notification Type 
OG - Object Group 
OI - Object Identity 
RO - Read Only 
RC - Read Create 
RW - Read Write 
TB - Table 
TE - Table Entry 
 

Содержание iBootBar iBP-N15

Страница 1: ...EMA 20 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBP 2N20 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control iBP 2N20 M 2 x NEMA 40 Amp 8 x NEMA 5 15 IP Control Serial Control Internal Modem iBP C10 IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control iBP C10 M IEC C14 10 Amp 8 x IEC C13 IP Control Serial Control Internal Modem iBP 2C10 2 x IEC C14 20 Amp 8 x IEC C13 IP Contr...

Страница 2: ... 4 Installation 5 Configuration 7 Basic Operation 9 Command Line Interface Direct Messaging Protocols Advanced Operations 14 Frequent Outlet Control Multi Outlet Control DTMF Control AutoPing Email Notification SNMP Firmware Upgrades Password Recovery Appendices Specifications 17 Compliance 18 Modem Certifications 19 SNMP MIB 20 Technical Support Returns Warranty 21 ...

Страница 3: ...defeat the safety purpose of the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product where the cord will be abused by persons walking on it 10 Do not overload wall outlets and extension cords as this can resul...

Страница 4: ...ity The iBP has many features to make the management of power distribution simple and cost effective 8 Independently controllable outlets Dual power inputs for redundant power feeds Support for dual redundant powered devices Naming of outlets for easy identification Multi Outlet control of outlets for simultaneous management Current monitoring with over and under alarm notification Multiple users ...

Страница 5: ... the iBP to the standard 19 inch rack Ethernet The iBootBar has a 10 100 Ethernet port The default address is 192 168 0 254 Serial Port The iBootBar has a 9 pin D subminiature connector for RS 232 serial control The connector is configured as DCE for direct connection to a laptop or other terminal device Default serial parameters are 115 200 bps 8 data no parity 1 stop bit 115200 8 n 1 Serial Port...

Страница 6: ...imum current load for all outlets cannot exceed 12 Amps at 115VAC or 10 Amps when used at 240VAC The iBP 2C10 M is for international applications and can be used on 100V to 240VAC The iBP 2C10 provides two IEC 320 style universal inlets for connecting a detachable power cord Two standard IEC to CEE7 European cord sets are supplied with the unit for use on 10 Amp 240VAC service The total maximum cu...

Страница 7: ...dem 2 Automatically from a DHCP Server 3 ARP Ping To configure the mode to set the IP address access the iBootBar command line interface CLI and use the set ipmode command as indicated below Setting the IP address using CLI The following commands are used to set the IP parameters set ipaddress dotted decimal ex 192 168 0 125 set subnet dotted decimal ex 255 255 255 0 set gateway dotted decimal ex ...

Страница 8: ...tted decimal for the iBootBar and the MAC address is the MAC Address of the iBootBar The MAC Address of the iBootBar is located on the rear of the unit Example arp s 63 211 86 165 00 50 c2 05 01 c1 enter new IP addr MAC addr 4 Ping the iBootBar to program the IP address into the iBootBar Type ping IP Address Note If the ping command returns host not responding 4 times then the address has not been...

Страница 9: ...cycle The cycle time is the length of the reboot or power on In seconds 0 99 set cycle n get console Display current console configuration set console timeout 30 3600 disable Console can be set to automatically logout with no activity for 30 seconds to 1 hr in seconds or disabled set console baudrate baud 2400 4800 9600 19200 38400 57600 115200 get autologin Enabled will allow admin rights without...

Страница 10: ... address of the iBootBar set ipaddress dotted decimal Set the current IP address ipmode must be set to static to use this command set subnet dotted decimal Set the Subnet Mask set gateway dotted decimal Set the Gateway get telnet Display current telnet enable telnet port parameters set telnet enable yes no Enable or Disable Telnet Server set telnet port 1 65535 Change the Telnet Server IP port def...

Страница 11: ...ne Byte status for each outlets all 8 Bytes of status for each command Verbose Status for controlled outlet only Basic Syntax esc pass esc outlet cmd esc pass outlet cmd CR iPAL Protocol esc pass esc outlet cmd Syntax definitions esc ASCII Escape Character Decimal 27 Hex 1B pass Password no username is required outlet Outlet number 1 8 A for All outlets cmd Command to be performed Commands E Turn ...

Страница 12: ...n Outlet ON C Cycle Outlet Cycle can be On Off On or Off On Off depending on starting status T Set Cycle Time Cycle time in seconds Valid range 1 99 Get Status Outlet number optional No outlet number will respond with status for all outlets Examples esc pass 1ON enter Turn on outlet 1 esc pass 3C enter Cycle Outlet 3 esc pass enter Status for all Outlets esc pass 5 enter Status for Outlet 5 Respon...

Страница 13: ...her on or off to improve product life expectancy for example set outlet 1 initial state on set outlet 4 initial state off Multi Outlet Control Command This command is used to operate all eight outlets simultaneously set outlets nnnnnnnn Where n is either 0 for off or 1 for on The command once typed reads from outlet eight to outlet 1 most significant to least significant set outlets 8 status 7 sta...

Страница 14: ...he key is used to reboot or power cycle the outlet for the time configured with the CLI command cycle time The new status of the outlet is stated If the key is used the iBootBar will also state begin to indicate the reboot or cycle has begun 5 A new prompt tone will indicate that new commands can be entered While a reboot is in progress additional outlets can be addressed and commanded 6 The calle...

Страница 15: ...llow Upon triggering iBootBar will power off the assigned outlet When the ping response returns iBootBar will power the outlet on Cycle Upon triggering iBootBar will cycle the power to the assigned outlet iBootBar will wait the Ping Frequency x Fail Count if the response does not return the power will be recycled again This will continue until the ping response returns or AutoPing is turned off Ma...

Страница 16: ...nabled using the set upload enable yes command on the console interface To upgrade the iBootBar download the latest version of the firmware and upgrade utility from the Dataprobe website http Dataprobe com ibootbartools html Password Recovery Holding the reset button on the front panel of the iBootBar for 5 seconds or longer will initiate a password recovery mode Once the reset button is released ...

Страница 17: ... M C14 8 x C13 I S M iBP 2C10 2 x C14 8 x C13 I S iBP 2C10 M 2 x C14 8 x C13 I S M iBP C20 C20 8 x C13 I S iBP C20 M C20 8 x C13 I S M iBP 2C20 2 x C20 8 x C13 I S iBP 2C20 M 2 x C20 8 x C13 I S M Key Input N15 NEMA 5 15 Linecord 115VAC 15 Amps combined total switched N20 NEMA 5 20 Linecord 115VAC 20 Amps combined total switched C14 IEC320 C14 Receptacle 100 240VAC 10 Amps total at 240VAC Max C20 ...

Страница 18: ...an for help This device complies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority t...

Страница 19: ...e current country setting Note Use of the wrong countrycode violates local laws and the warranty of this product Country countrycode Argentina 07 Australia 09 Austria 253 Belgium 253 Canada 181 China 181 Cyprus 253 Czech Republic 253 Denmark 253 Finland 253 France 253 Germany 253 Greece 253 Hong Kong 153 Hungary 253 Iceland 253 Indonesia 153 Ireland 253 Italy 253 Japan 00 Korea 181 Liechtenstein 2...

Страница 20: ...er32 delayTime 2 TB snmpManagerTable 1 TE snmpManagerEntry 1 RO Integer32 snmpManagerIndex 2 RW DisplayString snmpManagerIPAddress 3 RW INTEGER Enum snmpManagerEnable 3 TB outletTable 1 TE outletEntry 1 RO Integer32 outletIndex 2 RW OCTET STRING outletName 3 RO INTEGER Enum outletStatus 4 RW INTEGER Enum outletCommand 5 RO INTEGER Enum outletAPStatus 4 BR info 1 RO Integer32 currentLC1 2 RO Intege...

Страница 21: ...l Dataprobe Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORT...

Отзывы: