Power Switch 

Contact Control 

1.  General Description 

The iBoot-IO is a remote controlled power On / Off switch.   One external control input is used to switch the 
power ON and OFF.  The iBoot-IO also provides a feedback circuit to verify the current power status.   iBoot-IO 
handles worldwide power from 105-240VAC.  It is capable of switching up to 12 Amps at 120VAC and 10 
Amps at 220 VAC. Screw terminals provide connection to the contact closure control and feedback circuit.  
Power connections are made using supplied IEC-320 to NEMA 1-15 cables. 

1.1. 

Covered Models 

Four models are covered in this document.  They differ in the type of input circuit used to control the power and 
the default status of the power outlet when no control is provided.   
 

SKU  

Model 

Default Power 

Control Input Type 

1410037 

iBoot-IO 

ON 

Dry Contact 

1410039  

iBoot-IO-OFF 

OFF 

Dry Contact 

1410044  

iBoot-IO-LS 

ON 

+3 to +12 VDC 

1410045  

iBoot-IO-OFFLS 

OFF 

+3 to +12 VDC 

2.  Connections  

2.1. 

Connect Powered Device  

Connect the device to be powered ON and OFF to the IEC receptacle marked Switched Outlet. An IEC 320 to 
North American (NEMA 5-15) power cord is included for connecting the iBoot-G2 outlet to the device to be 
controlled.  
 

Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105-
125VAC or 10 Amps for 210-240VAC. 

 
Connect Power Mains

 Connect the supplied power cord to the connector labeled AC Input, and the other end 

to your AC source.   If a power cord with a different terminating plug is required, be sure it is properly rated and 
meets all the required local electrical standards.   
 
 
 
 
 
 

 

Other Power Cords  

Sourced Locally 

Connect to Power Mains using  

Supplied Cord 

 

Connect Powered Device using  

Supplied Cord 

Содержание iBoot-IO

Страница 1: ...efault Power Control Input Type 1410037 iBoot IO ON Dry Contact 1410039 iBoot IO OFF OFF Dry Contact 1410044 iBoot IO LS ON 3 to 12 VDC 1410045 iBoot IO OFFLS OFF 3 to 12 VDC 2 Connections 2 1 Connect...

Страница 2: ...gh Open Power OFF Low Ground Power ON G Ground Common Ground I Control Input Open Power ON Ground Power OFF 2 4 Model iBoot IO OFF 1410039 Default Power OFF Dry Contact Control iBoot IO OFF Function O...

Страница 3: ...Control Input Open 1 5 VDC Power ON 3 12 VDC Power OFF 2 7 Model iBoot IO OFFLS 1410045 Default Power OFF DC Voltage Wet Control iBoot IO OFFLS Function O Feedback Output High Open Power OFF Low Groun...

Страница 4: ...V181217N iBoot IO Page 4 3 LED Indicators LED OFF ON OK Green Power Main Disconnected Power Main Connected PWR Red Power Outlet Off Power Outlet On...

Страница 5: ...Installing the Wall Mounting Kit DIN Rail Mounting 1 Remove the four mounting screws from the underside of the unit Do not disassemble the unit 1 Install the Wall Mounting Kit as shown 2 Install the...

Страница 6: ...a three wire grounding type plug a plug having a third grounding pin This plug will only fit into a grounding type power outlet This is a safety feature If you are unable to insert the plug into the...

Страница 7: ...r this Warranty is obtained by contacting your Authorized Dataprobe Reseller THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EX...

Отзывы: