MAGTOP Snap 201
BISTABLE SWITCH
SAFETY INSTRUCTIONS
- Installation, commissioning and maintenance may only be performed out by qualified personnel!
- Only connect the device to the voltage specified in the technical data or on the type label!
- Disconnect the device from the power supply during installation/maintenance work!
- Only operate the device under the conditions defined in the operating instructions!
NOTICE!
- Only use BAMO IER floats, no foreign magnets, not even for testing purposes
- Always install the float with the "TOP" marking facing upwards
- Always mount the cable entry point downwards
- Before commissioning, check the switching contact (with continuity tester) that the contact position corresponds to the current tank level, if
necessary bring the contact with switching magnet into the correct position (see contact position).
- Stainless steel tubes may only be used if they are non-magnetic and seamlessly drawn. Welded stainless steel tubes are magnetic and
interfere with proper function
- Do not mount or store near strong magnetic fields or ferromagnetic parts (steel beams, struts, container parts, etc.)
DESCRIPTION
Connected to a MAGTOP series magnetic flap indicator, the bistable switches of the MAGTOP SNAP type serve as limit switches. If the
bistable switch is passed by the magnetic float running inside the indicator, it changes its position and switches. It can be freely placed along
the display area as required and, taking into account the minimum distance between two switches, any number of limit values can thus be
recorded.
TECHNICAL DATA
Switching principle
Magnetically actuated microswitch with changeover contact
Switching voltage
4...250V AC; 4...30V DC
Switching current
1mA...3A
Max. Fluid tempe160°C
with clamp: +115°C
Ambient temperature
-20...+90°C
Housing
Aluminum, protection class IP65, 80x75x58mm
Electrical connection
3-pole valve connector according to DIN EN 175301-803-A
CE marking: The device fulfills the legal requirements of the applicable EU directives
MOUNTING
Place the retaining foot on the left or right retaining rod, twist the MAGTOP Snap 201 so that the housing is in direct contact with the tube.
After adjusting the switching point, tighten the fastening screws on the retaining foot.
Maximum permissible distance between switch and standpipe is 1mm!
For small switching distances, always mount switches on the left and right.
Never mount two switches on top of each other without spacing!!!
LEV
10-05-2023
M-560.11-EN-AA
560-11
/1
BISTABLE SWITCH
MAGTOP Snap 201
22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL
Tel
Fax
+33 (0)1 30 25 83 20
+33 (0)1 34 10 16 05
Web
www.bamo.eu