SG2 MUTING
86/96
MOUNTING
Put the arm slider (1) into the column slot (2).
Fix the arm (3) in the desired position by screws (4), 1 Nm recommended tightening torque.
Fig 118 - Phase 1
Rotate sensors/reflectors support (5) in the desired position ; if necessary, translate support removing and
spacing cable-locker (6) and fix by screws (7), 2 - 3 Nm recommended tightening torque.
Fig 119 - Phase 2
Loosen the two screws (8) and rotate/set the sensor/reflector as desired, then fix by screws (8), 1 Nm
recommended tightening torque.
Fig 120 - Phase 3
For electrical link of SG-M kit to DATALOGIC safety curtains, is recommended to use
Datalogic Connection Box SG-M-CB.
For each muting system kit is recommended to use same sensors type.
Sensors must be set on Dark Mode.