 Fix the two units firmly using brackets. 

 Verify that the green LED (

) on the RX unit is ON and beams are not interrupted, then verify that the red LED 

(

) turns ON if even one single beam is interrupted (condition where an object has been detected). 

 This verification shall be made with the special cylindrical “Test Piece” having a size suitable to the resolution of the 

device used. 

 

NOTE: Passing the Test Piece along the whole sensitive area and at any distance from the two units, the red LED 
(

) shall be always ON and never change status. 

 
A daily test is recommended. 

 

DIAGNOSTIC FUNCTIONS 

The operator can visualise the operating condition of the light curtains through the four LEDs positioned on the receiver 
unit and two LEDs on the emitter unit. 
The figure below shows all signalling LEDs modes: OFF, ON and BLINKING. 
 

 

 
The operator is able to check the main causes of the system stop and failure, using the same LEDs used for visualising 
the functions. For Receiver: 

 

Function 

Status 

Meaning 

LED 

TEST 
(red ON) 

Light curtain being tested, the OSSD status shall be OFF 

 

Emission (OSSD ON) 
(green ON) 

Light curtain working and in normal operating conditions 

 

Normal 
operation 

Interruption (OSSD OFF) (red ON) 

Light curtain working and in safety block conditions.  

 

Function 

Type 

Check and repair 

LED 

OSSD error (yellow and red BLINKING) 

Check OSSD connections; make sure that they are not in contact with one 
another or with the supply cables, then Reset. If the failure continues 
contact DATALOGIC AUTOMATION 

 

Internal error (red ON 
yellow BLINKING) 

Switch OFF and switch ON the supply circuit; if the failure continues contact 
DATALOGIC AUTOMATION 

 

Optical error (red ON yellow BLINKING) 

Reset. If the failure continues contact DATALOGIC AUTOMATION 

 

Error status 

No power supply 
(LEDs OFF) 

Check connections and input voltage correct value. 
If the failure continues contact DATALOGIC AUTOMATION 

 

 
For Emitter: 

 

Function 

Status 

Meaning 

LED 

Test (green ON) 

Light curtain being tested, the OSSD status shall be OFF 

 

Normal 
operation 

Emission 
(green ON 
yellow ON) 

Light curtain working and in normal operating conditions 

 

Function 

Type 

Check and repair 

LED 

Internal error (green ON yellow 
BLINKING) 

Switch OFF and switch ON  the supply circuit; if the failure continues 
contact DATALOGIC AUTOMATION 

 

Optical error (green ON yellow blinking) 

Switch OFF and switch ON the power supply circuit. If the failure continues 
contact DATALOGIC AUTOMATION. 

 

Error status 

No power supply 
(LEDs OFF) 

Check connections and input voltage correct value. If the failure continues 
contact DATALOGIC AUTOMATION 

 

 

LED ON

LED OFF

 
 

LED BLINKING

Содержание SG2-B Series

Страница 1: ...e light curtain Precautions to be observed for the choice and installation of the device Make sure that the protection level assured by the SG2 device Type 2 is compatible with the real danger level of the machine to be controlled according to EN 954 1 and EN 13849 1 The outputs OSSD of the ESPE must be used as machine stopping devices and not as command devices The machine must have its own START...

Страница 2: ...tatus as shown in the table Correct alignment procedure The light curtain alignment can be effected only after having completed the mechanical installation and the electrical connections The following procedure has to be followed Check the green LED and the yellow LED on the TX unit If ON the emitter is running correctly Verify that the sensitive area from the safety light curtain is free Verify t...

Страница 3: ...d ON Light curtain working and in safety block conditions Function Type Check and repair LED OSSD error yellow and red BLINKING Check OSSD connections make sure that they are not in contact with one another or with the supply cables then Reset If the failure continues contact DATALOGIC AUTOMATION Internal error red ON yellow BLINKING Switch OFF and switch ON the supply circuit if the failure conti...

Страница 4: ...efective during the warranty period of 36 months from the manufacturing date This warranty does not cover damage or liability deriving from the improper application of DATALOGIC AUTOMATION products DATALOGIC AUTOMATION Via Lavino 265 40050 Monte S Pietro Bologna Italy Tel 39 051 6765611 Fax 39 051 6759324 www automation datalogic com e mail info automation it datalogic com DATALOGIC AUTOMATION car...

Отзывы: