MATRIX 300™ QUICK GUIDE
9
LEARN
6.
Enter the Learn function by pressing and holding the X-
PRESS™ push button until the Learn LED
is on.
7.
Release the button to enter the Learn function. The Learn LED will blink until the procedure is
completed.
The Learn procedure ends when the Image Processing and Decoding parameters are successfully
saved in the reader memory, the Green Spot is activated, the Learn LED will stop blinking and
Matrix 300™ emits 3 high pitched beeps
1
.
Figure 7
– X-PRESS™ Interface:
Learn Function
If the autolearning
cannot be reached after a timeout of about 3 (three) minutes Matrix 300™ will exit without saving the parameters to
memory, the Learn LED will stop blinking and in this case Matrix 300™ emits a long low pitched beep.
You can exit the Learn function at any time by pressing the X-
PRESS™ push button once. After a short delay the Learn procedure is
cancelled.
The Grade A Barcode Test Chart cannot be used to set the Code 128 symbology (even though the reader successfully reads the
code). Use the application specific code if you need to set this symbology.
If you have used this procedure to configure Matrix 300
™ go to step 7.
RESET READER TO FACTORY DEFAULT (OPTIONAL)
If it ever becomes necessary to reset the reader to the factory default values, you can perform this procedure by holding the X-
PRESS™
push button pressed while powering up the reader.
You must keep the X-
PRESS™ push button pressed until the power up sequence is
completed
(several seconds) and all LEDs blink simultaneously 3 times.
All LEDs remain on for about 1 second, then off for one second, the Configuration and Environmental parameters are reset, and the status
LED remains on. If connected through a CBX500 with display module, the message "Default Set" is shown on the display.
1
The Learn procedure will not recognize Pharmacode symbologies.