background image

  DSD-080 User Manual                                                                                         V-1.0

 

 

1

 

 

 

 DSD-080 

SEISMIC 

SECURITY 

PANEL

 

 

 

 

DATAKOM DSD-080 Seismic Security 
Panel monitors seismic motions of a 
strong earthquake and provides relay 
output signals from it. Output signals are 
used to shut-off critical installations as 
natural gas and LPG systems, 
generators, elevators and the like. 

The unit helps reducing damages of a 
probable earthquake. On its graphical 
display screen, the unit shows system 
status. 

DSD-080 incorporates highly sensitive 
triple axis seismic sensors. The unit is 
maintenance free and capable of making 
self-test.  

The earthquake sensing specifications of 
DSD-080 conforms to both ANSI Z21.80 
(1981), ASCE 25-97 and TS-12884(2002) 
standards.  

DSD-080 operates on mains with a battery 
backup. 24V/1.2A-h batteries are 
incorporated to the unit. The unit provides 
automatic battery charging feature. During 
long mains failures, if batteries get low, the 
unit gives audible and visible alarm. 

The unit provides 5 high power relay 
outputs. Through the programming menu, 
outputs may be assigned to any function 
selected from a list. 

 

 

• 

Wide operating voltage range  

• 

Conformal to earhquake standards 

• Triple

 axis motion detection 

• 

Automatic self-test 

• 

Internal audible warning 

• 

Internal 24V battery 

• 

5 programmable relay outputs (5Amp) 

• 

Visual indicators for battery status 

• 

Wide operating temperature range 

 

Sensor Specifications 
Sensor type: 

Triple axis polysilicon 

semiconductor acceleration sensors. 

Sensor operating limits:

 

±2g.  

Sensor failure limit: more than 

50g. 

Acceleration threshold: 

TS12884, ANSI 

Z21.80 (1981), ASCE 25-97 

Detection delay:

 0.5sn. maximum 

Frequency range: 

0.5Hz to 25Hz 

 

 

        

 

 

 

 

 

FEATURES

 

DESCRIPTION

 

Содержание DSD-080

Страница 1: ...with a battery backup 24V 1 2A h batteries are incorporated to the unit The unit provides automatic battery charging feature During long mains failures if batteries get low the unit gives audible and...

Страница 2: ...ument These are often good practices for the installation which reduce future issues For all technical queries please contact Datakom at below e mail address technical support datakom com tr REVISION...

Страница 3: ...ust be connected to phase voltage inputs in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment When the unit is conn...

Страница 4: ...N 2 3 ELECTRICAL INSTALLATION 2 4 INSTALLATION DIAGRAM 3 PUSHBUTTON FUNCTIONS 4 DISPLAYS 5 ALARMS 6 DEVICE CONFIGURATION 6 1 ENTERING THE PROGRAM MODE 6 2 CHANGING PARAMETER VALUE 6 3 LIST OF PARAMETE...

Страница 5: ...lugs to their sockets Otherwise you may destroy the socket and connector Be sure that the ambient temperature will not exceed the maximum operating temperature limit Below conditions may damage the de...

Страница 6: ...DSD 080 User Manual V 1 0 6 Dimensions 192x120x65mm WxHYxD Weight 1900g 2 INSTALLATION 2 1 DIMENSIONS 192mm...

Страница 7: ...DSD 080 User Manual V 1 0 7 The unit is designed for wall mounting Please mount on a flat surface through screw openings 2 2 MECHANICAL INSTALLATION WALL...

Страница 8: ...nected to phase voltage input in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0...

Страница 9: ...DSD 080 User Manual V 1 0 9 2 4 CONNECTION DIAGRAM...

Страница 10: ...arm relay are reset Used to navigate between menus Programming mode Increase related value Used to navigate between menus Programming mode Decrease related value HELD PRESSED TOGETHER FOR 3 SECONDS En...

Страница 11: ...it is operating normally BATTERY NORMAL LED Indicates that the battery voltage is above the Low Battery Voltage parameter LOW BATTERY LED Indicates that the battery voltage is below the Low Battery Vo...

Страница 12: ...ay outputs become active and the unit gives an audible alarm By depresing the RESET pushbutton alarms are reset and relays return to their initial position ALARM MESSAGE DESCRIPTION LOW BATTERY Occurs...

Страница 13: ...e memory and are not affected by energy failures In program mode the required parameter is selected using or pushbuttons By depressing the pushbutton the parameter modification is enabled Using and pu...

Страница 14: ...e LOW BATTERY Output closed when battery is low WEAK MOTION Output closed during a weak motion WEAK MOTION LATCHED Output closed during a weak motion Remains closed until manually reset WEAK MOTION SO...

Страница 15: ...r 4W maximum Battery charge voltage 27 5V 0 2V Battery charge current 100mA maximum Low battery voltage limit 22V 0 3V Current drain from battery 15mA max from 24VDC All relays passive Additional 6mA...