DPR-400 User Manual Rev_01 Firmware V-1.0
- 66 -
REGISTER
ADDRESS
VARIABLE
DESCRIPTION
SIZE
R/W
TYPE
X
20520
U31 RMS
U31 Phase
– Phase
Voltage
32
R-O
Unsigned
long
x10
20522
P1
Phase 1 Active
Power (kW)
32
R-O
Signed
long
x100
20524
P2
Phase 2 Active
Power (kW)
32
R-O
Signed
long
x100
20526
P3
Phase Active Power
(kW)
32
R-O
Signed
long
x100
20528
∑P
Total Active Power
(kW)
32
R-O
Signed
long
x100
20530
Q1
Phase 1 Reactive
Power (kVAr)
32
R-O
Signed
long
x100
20532
Q2
Phase 2 Reactive
Power (kVAr)
32
R-O
Signed
long
x100
20534
Q3
Phase 3 Reactive
Power (kVAr)
32
R-O
Signed
long
x100
20536
∑Q
Total Reactive
Power (kVAr)
32
R-O
Signed
long
x100
20550
Frequency
Frequncy
16
R-O Unsigned
word
x100
20576
Alarm
Function Alarm Bits
0-63
64
R-O
Long
Long
-
20580
Warning
64
R-O
Long
Long
-
20584
İnput
Input Status
32
R-O
Unsigned
long
-
20586
Output
Output Status
32
R-O
Unsigned
long
-
20588
Input Count
Number of digital
inputs
16
R-O Unsigned
word
x1
20589
Output Count
Number of digital
outputs
16
R-O Unsigned
word
x1
20590
LED Count
Number of LEDs on
the unit
16
R-O Unsigned
word
x1
20591
Reset_sta
Last Reset Cause
16
R-O
16 bit
bitmap
-
20592
-
Reserved
16
R-O Unsigned
word
x1
20593
Dig-in
OG Digital Input
Statuses
32
R-O
16 bit
bitmap
-
20595
Matrix
Status information
for matrix inputs
8x16
R-O
128 bit
bitmap
-
20603
DeviceID
Device type
(0xD400)
16
R-O Unsigned
word
-
20604
HWVersion
Hardware Version
16
R-O Unsigned
word
-
20605
SWVersion
Software Version
16 BIT
R-O Unsigned
word
-