DPR-145 User Manual V-3.0
(14.09.2016)
-15-
DISPLAY
DESCRIPTION
MIN
MAX
FAN OFF PARAMETER (
)
Adjusts Fan Turn OFF Temperature.
0
295
ALARM ENABLE PARAMETER
(
)
0:
No alarm is generated from this
channel
1:
if the temperature read from this
channel is over Alx limit, then an alarm is
generated.
0
1
RS-485 DATA RATE: (bdr)
0: 2400 baud 5: 28800 baud
1: 4800 baud 6: 38400 baud
2: 9600 baud 7: 56000 baud
3: 14400 baud 8: 57600 baud
4: 19200 baud 9: 115200 baud
0
9
MODBUS NODE ADDRESS (nod)
This parameter defines the address of
the unit in a Modbus network. Each
device in the same network must have a
different address.
0
255
For any channel, the difference between Alarm and Trip
temperatures cannot be less than 5 degrees C and the Trip
temperature is always higher than Alarm temperature.
The same way, the difference between Fan Turn ON and Turn
OFF parameters cannot be less than 5 degrees C and Fan
Turn ON is always higher than Fan Turn OFF.