J38D01 - 26 -
2.18 RETURN TO FACTORY SETTINGS
It is possible to reset the unit to factory settings,
before starting a new configuration process.
For this select “
RETURN FACTORY
” on
“
CONFIGURATION MENU
”.
Then select “YES” and press
to reset the unit
to factory configuration and return to
“
CONFIGURATION MENU
”.
2.19 CALIBRATION
Calibration can be modified only with a special password.
The unit is factory calibrated but it is possible to
recalibrate it in order to obtain equal display values
on different measuring instruments.
Select “
CALIBRATION
” on “
CONFIGURATION
MENU
”. Then select channel with
and
,
and then press
.
Then adjust the coefficient until required measured
value is displayed on the bottom right of the screen
then press
to save the new calibration
coefficient and return “
CONFIGURATION MENU
”.
CHANNEL
MEASUREMENT