background image

 

Supply Input:

 100-240VAC 

(±15%), 50/60Hz 

Measurement Inputs: 

 

    Voltage:     

7 - 300 V AC (P-N) 

  

14 - 520 V AC (P-P) 

    Current: 

0.001 

– 6.00 A AC  

    Frequency:  

30 - 100 Hz

  

Accuracy:

  

 

    Voltage, current:  

0.5% + 1 digit 

    

Frequency:

   

0.5% + 1 digit 

    Power 

(kW,kVAr)

:

1.0%  + 2 digit 

    Cos:  

     

   

0.5% + 1 digit 

Withstanding: 
    Current: 

100 A AC during 1 sec. 

    

Voltage: 

1300 V AC (continuous) 

Analog Outputs: 

Active 4-20mA, 16 bit 

Measurement Range: 

 

    CT range:

      

5/5A to 25000/5A  

    VT range:

      

0.1

/

1 to 5000.0

/

    kW range:

     

1.0 kW to 5000 MW 

Power Consumption:

  

< 15 VA  

 

Voltage Burden: 

< 0.02VA per phase 

Current Burden: 

< 0.5VA per phase 

Relay Outputs: 

5A @ 250V AC

 

 

Digital Inputs: 

 

 

    Active level: 

24 to 135V-DC or AC  

    Min pulse:  

250ms.  

    Isolation: 

1000V AC, 1 minute 

Serial Port:

  RS-485, 2400-115200 bauds   

    Protocol: 

Modbus RTU 

    I

solation: 

500V AC, 1 minute 

Operating Temp. Range:

   

    -

20°C to +70 °C (-4°F to 158°F) 

Max Humidity: 

95%, non-condensing

 

IP Protection: 

IP 54 (Front), IP 30 (Back) 

Enclosure: 

Non-flammable, ROHS compl. 

Installation:

 Flush mounting 

Dimensions: 

102x102x53mm (WxHxD) 

Panel Cutout: 

92x92mm 

Weight:

 200 gr 

EU Directives:

  

2006/95/EC (LVD)

 

2004/108/EC 
(EMC) 

Norms of Reference:

 

EN 61010 (safety) 
EN 61326 (EMC) 

UL-CSA Certification: 

UL 61010-1, 3rd Edition, 2012-05,  
CAN/CSA-C22.2 
File: E475547, Vol. D1 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TECHNICAL SPECIFICATIONS 

 

CONNECTION DIAGRAM 

 

Отзывы: