DKG-329 User Manual V-12
(09.10.2012)
- 28 -
Program Group: Controller Configuration (continued)
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(1)
Exercise Duration
min
10
This parameter defines the exercise duration and
programmed in 10 minute steps up to 24 hours.
(1)
Exercise Off/On Load
-
0
0:
Exercise at
TEST
mode
1:
Exercise at
LOAD TEST
mode
(1)
Exercise Period
-
1
0:
exercise every day (the exercise will be performed
every day regardless of the day selection of Exercise
Dat and Time parameter).
1:
exercise once per week
2:
exercise once per month (the exercise will be
performed during the first 7 days of each month at
the programmed day and hour).
(2)
Delayed Simulate Mains
-
0
0:
The
SPARE-2
input has normal function
1:
The
SPARE-2
input has delayed simulate mains
function. See chapter 7.3for more info.
(2)
Modem Enable
-
0
0:
No modem connection, the serial port is connected
to PC
1:
Modem connected.
(2)
SMS Enable
-
0
0:
SMS not enabled
1:
SMS enabled
(2)
MODBUS Address
-
0
0:
RAINBOW communication protocol.
1-144:
MODBUS communication. This parameter is
also the MODBUS controller address of the unit.
(1)
Real Time Clock Adjust
-
117
This parameter trims precisely the real time clock
circuit.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
(2)
Hysteresis Voltage
V
8
This parameter provides the mains and genset
voltage limits with a hysteresis feature in order to
prevent faulty decisions.
For example, when the mains are present, the mains
voltage low limit will be used as the programmed low
limit. When the mains fail, the low limit will be
incremented by this value. It is advised to set this
value to 8 volts.
(2)
SMS on Mains Change
-
0
This parameter controls SMS sending when mains
voltages status is changed. No warning is generated.
0: no SMS when mains failed or restored
1: SMS sent when mains failed or restored