DC SUPPLY:
12 or 24 volts DC, (+) and (-) terminals.
L1:
Generator phase voltage.
NEUTRAL:
Generator neutral terminal.
HIGH TEMP SWITCH:
Negative closing switch input.
LOW OIL PRESSURE:
Negative closing switch input.
AUX:
Spare fault input. A negative supply connection
to this input will cause the engine immediately stopped
and an alarm given (independent of the protection
hold-off timer).
CHARGE:
Connect the charge alternator’s D+ end to
this terminal. This terminal will supply the excitation
current and measure the voltage of the charge
alternator.
FUEL SOLENOID, START, AUXILIARY:
These are
fully protected, negative pulling solid state outputs.
Each output is rated 1.2amps@28V-DC.
JUMPER SELECTABLE STANDARD
FEATURES:
Genset control,
Activate to Start,
Energize to Stop,
50Hz nominal,
60Hz nominal.
OPTIONAL FEATURES:
(SUBJECT TO SPECIAL ORDER)
Engine control (without alternator),
Remote start input,
High power relay outputs (DKG-151).
Alternator Voltage:
15 to 300 V-AC
Alternator Frequency:
50 or 60 Hz nominal.
Overspeed:
nominal fre 14%
(+24% overshoot)
Underspeed:
25Hz
DC Supply Range:
8 to 33 V-DC.
Current consumption:
80mA max. (Relay outputs
open).
Charge fail threshold:
6 V-DC.
Charge excitation current:
via 82 ohms resistor
connected to the
FUEL
output.
Stop Timeout:
30 sec.
Operating temp.:
-20
C (-4
F) to 70
C (158
F).
Storage temp.:
-30
C (-22
F) to 80
C (176
F).
Maximum humidity:
95% non-condensing.
Dimensions:
72x72x38mm (WxHxD)
Panel cutout dimensions:
68x68 mm
Weight:
100g (approx.)
Installation:
Front panel mounted. Retaining steel
spring provided.