Installation
E F 3 0 1 5 S e t u p G u i d e ( R e v A )
15
AC model
See
when performing the following steps:
1.
Verify that the enclosure’s power switches are in the Off position.
2.
Identify the power cord connector on the PSU, and locate the target power source.
3.
Using the AC power cords provided, plug one end of the cord into the power cord
connector on the PSU. Plug the other end of the power cord into the rack power source.
4.
Verify connection of primary power cords from the rack to separate external power
sources.
See
.
DC model
Connector (front view)
Power cable (right side view with sectioned cutaway and wire breaks)
+L
GND
-L
+L
GND
-L
+L
GND
-L
Connector pins (typical 2 places)
Ring/lug connector (typical 3 places)
(+)
(-)
Ground
Figure 6. DC Power Cable Featuring D-Shell and Lug Connectors
See
when performing the following steps:
1.
Locate and use the provided DC power cables.
2.
Verify that the enclosure’s power switches are in the Off position.
3.
Connect a DC power cable to each DC power supply using the
D-shell connector. Use the
UP>
arrow on
D-shell
(left side view)
the connector shell to
ensure proper positioning (see adjacent left side view of D-shell
connector).
4.
Tighten the screws at the top and bottom of the shell, applying a
torque between 1.7 N-m (15 in-lb) and 2.3 N-m (20 in-lb), to securely
attach the cable to the DC power supply module.
5.
To complete the DC connection, secure the other end of each cable wire component of
the DC power cable to the target DC power source.
Check the three individual DC cable wire labels before connecting each cable wire lug
to its power source. One cable wire is labeled
ground
(GND), and the other two are
labeled
positive
(+L) and
negative
(-L), respectively
C
AUTION
:
Connecting to a DC power source outside the designated -48VDC
nominal range (-36VDC to -72VDC) may damage the enclosure.
See
.