Wiring Signals to the Module
33
Preparing to Wire Signals
This section provides recommendations and information about wiring signals to a DT9816
Series module.
Wiring Recommendations
Keep the following recommendations in mind when wiring signals to a DT9816 Series
module:
• Follow standard ESD procedures when wiring signals to the module.
• Use individually shielded twisted-pair wire (size 16 to 26 AWG) in highly noisy electrical
environments.
• Separate power and signal lines by using physically different wiring paths or conduits.
• To avoid noise, do not locate the box and cabling next to sources that produce high
electromagnetic fields, such as large electric motors, power lines, solenoids, and electric
arcs, unless the signals are enclosed in a mumetal shield.
• Prevent electrostatic discharge to the I/O while the box is operational.
• Connect all unused analog input channels to analog ground.
Wiring Signals to the DT9816, DT9816-A, DT9816-S, or
DT9816-S-WTR Module
To wire signals to a DT9816, DT9816-A, DT9816-S, or DT9816-S-WTR module, use the screw
terminals on the module, shown in
.
Содержание DT9816 Series
Страница 1: ...DT9816 Series UM 21336 X User s Manual Title Page ...
Страница 4: ......
Страница 8: ...Contents 8 ...
Страница 12: ...About this Manual 12 ...
Страница 13: ...13 1 Overview Key Hardware Features 14 Supported Software 16 Getting Started Procedure 19 ...
Страница 20: ...Chapter 1 20 ...
Страница 21: ...Part 1 Getting Started ...
Страница 22: ......
Страница 44: ...Chapter 3 44 ...
Страница 54: ...Chapter 4 54 ...
Страница 55: ...Part 2 Using Your Module ...
Страница 56: ......
Страница 57: ...57 5 Principles of Operation Analog Input Features 59 Digital I O Features 64 Counter Timer Features 65 ...
Страница 81: ...81 7 Troubleshooting General Checklist 82 Technical Support 84 If Your Module Needs Factory Service 85 ...
Страница 86: ...Chapter 7 86 ...
Страница 102: ...Appendix B 102 ...
Страница 108: ...Index 108 ...