6.3 Precautions at the time of wiring
※
At the time of module wiring, make sure to check the input voltage range of inverter and temperature coefficient
of module.
※
At the time of cable wiring to the terminal block, make sure to use compression terminal (O or U type). There is
a possibility of inducing fire due to defective contact if cable is connected directly.
※
Fuse will melt and short circuited due to exceeding of allowed current if (+) or (-) cable is used commonly. Make
sure to wire the cable in accordance with the cable-wiring diagram.