![DARLEY ZSP Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/darley/zsp/zsp_nstallation-operation-maintenance-repair-and-troubleshooting-instructions_510501037.webp)
TABLE NO. 1
NFPA 1901 TEST
TEST
Recom-
Min.
Min.
Min. Net
Disch.
Suction
No.
GPM
mended
Nozzle
Disch.
Pump
Lines
Hose
Nozzles
Press. PSI
Press. PSI
Press. PSI
1
2500
(2), 2-1/4”
69
144
150
(2 Groups)
(3), 100’
2
1750
(2), 2”
55
195
200
Siamesed
3
1250
(2), 1-1/2”
88
246
250
4
2500
(2), 2-1/4”
69
159
165
1
3000
(2), 2-1/2”
65
146
150
(2 Groups)
(3), 100’
2
2100
(2), 2”
78
196
200
Siamesed
3
1500
(2), 1-3/4”
68
247
250
4
3000
(2), 2-1/2”
65
161
165
1
3000
(2), 2-1/2”
65
96
100
(2 Groups)
(3), 100’
2
2100
(2), 2”
78
146
150
Siamesed
3
1500
(2), 1-3/4”
68
197
200
1
3500
(2), 2-1/2”
and
45
95
100
(2 Groups)
(3), 100’
(1), 2-1/4”
44
Siamesed
2
2450
(2), 2-1/4”
67
146
150
&
3
1750
(2), 2”
55
197
200
(2)-50’
Siamesed
Class A
Min. discharge pressures listed above are for pumps operating with full 10’ static suction lift. These
pressures must be increased by 1 PSI for each 2.3 ft. less than 10’ of lift.
(2) 20’ of 8”
2500 GPM Fire Pump
20’ of 8”
3000 GPM Fire Pump
(2) 20’ of 8”
3500 GPM Industrial Fire Pump
3000 GPM Industrial Fire Pump
(2) 20’ of 8”
IF FURTHER INFORMATION IS NEEDED, CALL W.S. DARLEY & CO. AT
CHIPPEWA FALLS, WI. AT 800-634-7812 or 715-726-2650
Prepared by: CJC
Approved by: WAH
Revised by: CWY
4
Rev. #: 4
Date: 7/8/13
1201500
Содержание ZSP
Страница 64: ......
Страница 66: ......
Страница 67: ...DRIVELINE INSTALLATION J3311 1 DSSP AUGUST 2008 Supersedes J3311 1 HVTSS Dated February 2005 ...
Страница 89: ......
Страница 130: ......
Страница 133: ......
Страница 135: ...7 31 1200503 ...
Страница 136: ...7 32 1200503 ...
Страница 139: ...7 35 1200503 ...
Страница 140: ...7 36 1201002 ...
Страница 142: ...7 66 ...
Страница 143: ...7 65 ...
Страница 144: ......
Страница 146: ......
Страница 147: ......
Страница 148: ......
Страница 149: ......
Страница 150: ......
Страница 151: ......