background image

R

www.danvex.fi

Technical data of

 AD-

55

0

о

Moisture output

 0,6 

kg

/

hour

 (

at

 +20 C 

and RH

 60%)

Table

 2

 

Commissioning

Start up procedures

:

1. 

Make sure the dehumidifier is disconnected from the power supply source and that its main 

switch is in 

 

OFF position

.

2. 

Open the dehumidifier service panels and make sure there are no foreign matters inside 

the dehumidifier. 

3. 

Make sure all air throttles are opened and that channels are clean and  not blocked

.

4. 

Make sure that air filters are installed and clean

.

5. 

Manually turn the fans impellers and make sure they rotate freely

.

6. 

Check the internal fuse.

7. 

Close the service panels and connect the dehumidifier to 230V power supply. 

8. 

For the dehumidifier to operate in manual mode turn the switch to I

 (

MAN

)

 position

.

9.

 For the dehumidifier to operate in automatic mode turn the switch to II

 ( AUTO)

 position

.

 

The indication on the controller will light up

:

 upper line

 – 

current relative humidity

bottom line 

- set relative humidity

.

 Using 

◄►,

,

 buttons set the required RH value

,

 when doing so 

«5

d

»

 should be displayed in the upper line

,

 the bottom line should display the value being 

set

.

Then set the humidity change value (relative to the set value) at which the dehumidifier 

will turn on to maintain the set humidity level 

(

in the upper line of the display 

 «

SH

С»

 will be 

displayed

,

 in the bottom line the humidity change value will be displayed (delta)

.

10. 

To turn the dehumidifier off set the switch to OFF position

 (

middle position

).

11. 

After turning off the dehumidifier fans can continue operation for some time till the 

adsorption rotor cools down to the required temperature.

Dehumidified air

*

Rated air consumption

3

m

/

hour

8

580

Parameter

Unit

Value

Reactivation air

*

Rated air consumption

3

m

/

hour

200

Electric power and rated current

Total power
Voltage

 (1 

phase

,

 50 

Hz

)

kW

V

3.8

2

3

0

Reactivation air heater

Heater capacity
Heater type 

kW

-

3.1

РТС

Miscellaneous data 

Maximum sound pressure level
Operational temperatures range
Standard filter

:

 dehumidified air

R

   

eactivation air 

IEC protection, the whole dehumidifier  

dB(A)

о

С

-
-
-

6

1

–20…+

4

0

EU3
EU3

IP44

о

3

The above mentioned values are nominal based on the air temperature of 

20 С 

and the air density of 

1,2

kg

/

m

Содержание AD-550

Страница 1: ...DanVex AD 550 Adsorption air dehumidifier Operation manual...

Страница 2: ...R www danvex fi...

Страница 3: ...instructions 3 Introduction 4 Purpose 4 Design 4 Control board introduction 5 Operation principle 6 Dimensions and weight 6 Installation 7 Technical data 8 Commissioning 8 Maintenance 9 Transportatio...

Страница 4: ...osion hazard Before opening any panels of the unit body it is required to disconnect the dehumidifier from the mains Before starting any maintenance works the dehumidifier should be out of operation f...

Страница 5: ...licaGel and assures a very large contact area with air flow for moisture adsorption in the small volume of the rotor This material is highly efficient for water molecules attraction and retention it i...

Страница 6: ...re are three numbers totally in the screen shows the ambient RH level it testing lower LED screen there are three numbers in the screen shows the setted RH level c State of setting up Click O button t...

Страница 7: ...umidification process is assured The air flow used for the rotor matrix regeneration is called regeneration air REGENERATION AIR It is heated up to 120 and when passing through a small sector it remov...

Страница 8: ...stall the moist air duct upright it should be insulated and drain holes should be drilled in the lowest part of the elbow bend 2 4 mm Regeneration air duct The regeneration air duct should be as short...

Страница 9: ...required RH value when doing so 5d should be displayed in the upper line the bottom line should display the value being set Then set the humidity change value relative to the set value at which the de...

Страница 10: ...once per month Never use the dehumidifier without filters Rotor The rotor is maintenance free However for cleaning purposes it can be flushed out by compressed air A rotor cleaning procedure requires...

Страница 11: ...tions when it supplies the Customer a repaired or a spare part Parts repair or replacement does not result in the warranty period extension The parts and components replaced under the warranty belong...

Страница 12: ......

Отзывы: