Preventive maintenance 

 

Introduction 

The unit needs preventive maintenance with specific intervals to avoid breakdown or 
inefficient operation. It is important to notice that interval between maintenance can 
vary depending on the specific environment. 

Caution! 

Switch off all power to the unit before working on the unit! 
Make sure that all work has been performed before switching on the power again. 

Interval 

Kontrollelektronik Dantherm Air Handling AB recommends that intervals between 
preventive maintenance do not exceed 1 year. It is also our recommendation that the 
site and unit is examined closely during the first preventive maintenance to determine 
whether the interval is too long. We recommend that preventive maintenance visits are 
planned to occur in springtime. 

Condition for 
warranty 

The factory warranty is only valid if documented preventive maintenance has been 
carried out with an interval of maximum 1 year. The documentation could be in form of 
a written log. 

Recommended 
approach 

The recommended approach when performing a preventive maintenance visit is: 

 

Step 

Action 

Make sure that the power to the unit is safely switched off. 

Remove the worn-out filter and clean the unit carefully. 

Clean the dampers and check them regarding function and tightness. 

Clean the fan and check its mounting. 

Check and clean the air intake and exhaust accessories. 

Insert the new filter carefully into the unit. 

Close the unit and make sure that the service is completed correctly. 

Turn on the power to the unit. 

 

 

Function tests 

Fan and filter alarm function tests can be done by the following actions. 

 

Function test 

Action 

Filter 

Open the service door and put a plate of carton or similar on the 
intake side of the filter, blocking a big part of the filter area. Close the 
service door, run the free cooling unit and check that filter alarm is 
given. Stop and remove the plate. 

Fan 

Open the lid to the controlling unit and remove one of the cables 
connected to the connector marked “Tc1” or “Tc2”. Close the lid, run 
the free cooling unit and check that fan alarm is given. Restore the 
controller. 

 

 

Содержание KONTROLLELEKTRONIK FCB 773

Страница 1: ...U Manuals FCB FCB 773 EN pdf 1 10 2009 02 05 Free Cooling Box FCB 773 Service manual...

Страница 2: ...e 9 Spare parts list 10 Contact In the table below you can see how to contact the manufacturer and sales offices Office Sweden Norway Denmark Name Kontrollelektronik Dantherm Air Handling AB A S Danth...

Страница 3: ...006 95 EG Low Voltage Directive including 93 68 EEC where required 86 336 EEC EMC Directive including 92 31 EEC and 93 68 EEC 89 392 EEC Machine Directive The product is manufactured according to SS E...

Страница 4: ...280 W 275 W Sound pressure at 3m from shelter Approx 40dBA Approx 40dBA External available pressure drop 50 Pa 50 Pa Cabinet data Data of the cabinet are shown in the following table Specification Des...

Страница 5: ...filter Type Compact filter Removal efficiency F5 Dimensions 670 x 295 x 70 Total Area 4 3 m2 Filter monitor setting 85 Pa at 6V DC signal Controlling The table below show the components and types for...

Страница 6: ...U Manuals FCB FCB 773 EN pdf 6 10 2009 02 05 Dimensions Illustration This drawing illustrates the dimensions of the Free cooling unit Side Front...

Страница 7: ...U Manuals FCB FCB 773 EN pdf 7 10 2009 02 05 Flow illustration Flow The picture below schematically shows the air flow Default inlet Alternative inlet...

Страница 8: ...A2 PA1 Brown Blue 3 4 5 6 7 Brown White Blue White Green Tc 0 10V Tc 0 10V 1 2 6 5 Green 1 3 t 2 Fan alarm output Brown White BCT 48 0 100 Room termostat Fans Main supply 48VDC BCT 48 090120 PA2 Viole...

Страница 9: ...The documentation could be in form of a written log Recommended approach The recommended approach when performing a preventive maintenance visit is Step Action 1 Make sure that the power to the unit i...

Страница 10: ...In the table below you can see how to contact the manufacturer and sales offices Office Sweden Norway Denmark Name Kontrollelektronik Dantherm Air Handling AB A S Dantherm avd Kontrollelektronik Danth...

Отзывы: