24
Setting operation parameters
The HCV 400 unit utilizes an USB-B connection, for changing the units parameters via Dan-
therm PC-Tool/ MS Windows PC .
Check that the unit is working as it should and that 230V can easily be connected and discon-
nected .
The following tools are necessary for updating the HCV 400 unit firmware
• Computer (PC) with Windows and an available USB slot
• USB cable- USB_A to USB_B plugs (printer cable)
• Dantherm PC-Tool
Follow this procedure to connect the PC and HCV 400 unit:
Step Action
1
Turn on the Computer
2
Install PC Tool – this can be ordered from your Dantherm dealer .
3
Power on HCV 400 with no USB cable connected .
4
Connect USB cable
5
Start PC-Tool
6
Login
Start Dantherm PC-Tool and select your unit on the start screen, select: “connect” .
Log in with:
• Installer
= “1234”
• User
= password is not necessary
Air volumes – supply air and extracted air should always be adjusted so that they
comply correctly with the ventilation level in accordance with legislation .
Go to calibration tab in PC-Tool to adjust the fan level .
Fig . 12
Introduction
Preparation
Tools needed
Connection
Log in
Mandatory
parameter
changes
USB connections