Energy save
Mode
(Freecooling >
A/C)
If outdoor temperature is less than 1°C colder than indoor room temperature the
Fan will stop.
The connected Air-con units will start and stop according to the table above
.
Description
Value
Off
Temperature when fan stops
20
On
Temperature when Fan starts
23
Min °C
temperature at bottom of P-band
25
Max °C
Temperature at top of P-band
29
Set Point
The wanted indoor temperature; fan
speed will be adjusted between Min°C
and Max °C
27
A/C 1 on
External Air Con unit 1 start if connected
31
A/C 1 off
External Air Con unit 1 stops if connected
29
A/C 2 on
External Air Con unit 2 start if connected
33
A/C 2 off
External Air Con unit 2 stops if connected
31
Emergency on
Fan run 100% and both A/C 1 and A/C 2
starts
38
Emergency off
Fan stops both A/C 1 and A/C 2 continue to
run
36