Introduction
The DFC unit is by default set up to operate in one of the following free cooling modes:
•
Standard configuration (for DFC 350-450 AC/DC)
•
DFCNOMIN configuration or
•
DFCMINSP configuration
Mode can be changed using the CC 3000 controller.
Free cooling mode
The basic operation strategy can be described in the following way:
•
Connected heater (optional) starts, when temperature is too low (on/off set
points for heater can be adjusted).
•
Free cooling unit(s) start(s) up slowly, when temperature rises above Min °C
set point and fan will increase speed gradually (according to P-band) until Max
°C set point is reached.