3.2 Info pages
Touch the black info button and you can now see two pages with information´s about the unit. There
will be no information`s about the compressor on a DanX XD unit.
3.3 Setpoint pages
Touch the green tool button and you will be asked for a password which is
2222
.
You will now be able to set in the correct setpoints for the unit.
1)
The set points for room temperature and relative humidity for occupied and unoccupied
pool hall
2)
Air volumes for supply, return and minimum outdoor air
3)
Minimum and maximum supply temperature
IMPORTANT:
To activate the set points from the touch panel, you must set the point “BMS_SP_CONTROL” in
the MVC80 controller to YES. See chapter 4.0