DC power

直流电源

直流电源

直流电源

直流电源

 

Place the main power cable, and connect it to the 48VDC power supply. 

放置并连接好直流

48

伏电源线。

 

Start-up

启动

启动

启动

启动

 

Turn on the power and the internal fan start running. External fan Will start running when the temperature 
which in the condenser middle is above 35 ºC. 

开启电源,内风扇将即时运转,外风扇在冷凝器中部温度超过

35 ºC

后启动。

 

Demounting

拆卸

拆卸

拆卸

拆卸

 

If the unit by any need should be demounted the steps below should be followed: 

 

Uninstall the main power cable from power supply. (Make sure that the power supply is powered off) 

 

Demount all screws on the flanges. 

 

Take off the air-conditioner. 

在需要拆卸时,请按照下面的步骤拆卸:

 

 

卸掉主电源线。(确保供电电源关掉)

 

 

拆卸法兰上所有螺丝。

 

 

卸下空调。

 

3 Identification of the Unit 

机器的识别

机器的识别

机器的识别

机器的识别

 

All units have a silver type plate label, where all the important information about the specific unit can be 
found. Also the Dantherm address and phone numbers are printed here so the contact can be made on the 
site. 

所有空调都贴有标明机器规格的重要信息的标签。在标签上也有丹腾公司的地址和电话号码。

 

Serial number

序列号

 

Especially the serial number is important, and should always be mentioned when Dantherm is contacted 
about issues concerning the specific unit. 

序列号尤其重要,当涉及到丹腾公司机器的细节问题时都会用到该序列号。

 

 

 

 

 

 

 

Содержание DAC20-450D

Страница 1: ...C20 450D DAC20 450D Dantherm Air Handling Suzhou Co Ltd Address No 855 Zhu Jiang Rd SND Shi Shan Industrial Belt Suzhou Jiangsu China Phone 86 512 66678500 Fax 86 512 66678501 Homepage www dantherm ai...

Страница 2: ...Revision History Revision Description Date Author A First design Reed Wu 2010 06 01 01 Release Reed Wu 2010 10 08 Tom Sun 2010 12 22...

Страница 3: ...N OF THE UNIT 6 4 DESCRIPTION OF FUNCTIONALITY 7 GENERAL DESCRIPTION 7 TEMPERATURE 8 SET POINTS 9 COMPRESSOR OPERATION 9 HIGH TEMPERATURE ALARM 10 CONDENSER FAN OPERATION 10 INTERNAL FAN OPERATION 10...

Страница 4: ...eventive maintenance Usage of the product The DAC20 450D is especially designed for cooling of electronic equipment and for outdoor installation The unit must not be used for other purposes under any...

Страница 5: ...equipment part 2 2 specification of environmental tests transportation ETS 300 019 1 1 Equipment engineering environmental conditions and environment tests for telecommunications equipment part 1 1 c...

Страница 6: ...cted with foam Then per Thirty units are carried in a wooden package PE Contents in the package The DAC20 450D air conditioner is delivered with an installation kit with the following content DAC20 45...

Страница 7: ...be with clip lock at the bottom of the body and stick the sponge strip on inside flanges Lift the unit up and place it in the wall of cabinet mount the brackets and flanges with M6 bolts nuts fixing u...

Страница 8: ...he main power cable from power supply Make sure that the power supply is powered off Demount all screws on the flanges Take off the air conditioner 3 Identification of the Unit All units have a silver...

Страница 9: ...r to the refrigerant and exhaust to the ambient air through the condenser coil The closed loop internal circuit protects the enclosed equipment all types of hostile environments and control the intern...

Страница 10: ...o cool down the electronic equip ment Return air temperature is the temperature of the air entering the air conditioner from the electronic equipment Ambient air temperature is the outside air tempera...

Страница 11: ...If the return air drops to the set point 3 C compressor stop 3 C Compressor operation Failure indications 1 If the current to the compressor is missing the compressor running again after 30 second if...

Страница 12: ...The condenser fan is stopped until cooling is needed When the compressor starts the main board can feel condenser temperature when condenser temperature above 35 C condenser fan will also start 35 Int...

Страница 13: ...350 Pressure Operation Pa Operating pressure 101 3 70 106 Disp Pa Estimated pressure drop internal 80 Drop Pa Pressure drop in climate unit int 80 Temperature Tcooling C Cooling set points 25 20 40 t...

Страница 14: ...Tools Like a car the units need to be maintained with at regular interval to prevent an overheated situation causing the BTS to shut down Also lack of maintenance could cause unnecessary pollution to...

Страница 15: ...isit is Step Action 1 Make sure that the power to the unit is safely switched off 2 Clean the unit carefully for dust especially at Air ducts Fans Condenser and evaporator coils 3 Perform a test simul...

Страница 16: ...e corrosion and show no obvious signs of leakage Are the coil lamellas clean and undamaged Are all fan blades free of obstructions cracks missing blades and in balance Do the fans rotate freely and ar...

Страница 17: ...running smoothly so only replace if the component is faulty DAC20 450D Before the demounting the old spare part it is very important to order the new spare part from Dantherm To do this most effectiv...

Страница 18: ...Screwdriver T20 Step1 Step2 Step3 Remove the Cover screws Remove the connecter Remove 4 screw and take off internal fan Step Action 1 Remove internal cover install screw see step1 1 2 Remove the conn...

Страница 19: ...Action 1 Remove screws fixing the inside cover same as replacing the internal fan 2 Unplug the connector and remove four screws on external fan cover plate 4 3 Replace the external fan Replacing the...

Страница 20: ...rtified cooling technician should carry out the evacuation by using the necessary evacuation and recycling equipment If the refrigerant gas is not to be recycled by the evacuator it must be passed on...

Страница 21: ...ould be left to the local scrap dealer PCB Metal parts The metal parts are uncritical to scrap and can be left to local scrap dealer A few parts might have a thin visible layer of PVC foam insulation...

Страница 22: ...20 Wiring diagram...