30
Driver for rotor exchanger,
continued
Jumpers,
continued
Max. motor speed – jumper 2
Model
Rotor diameter,
mm
Motor speed, RPM
J2 Setting
BasX 6
1250
150
ON
BasX 10
1550
200
OFF
BasX 14
1950
150
ON
Jumper 1, motor
rotation
Direction of motor rotation for rotor exchanger – jumper 1
J1: OFF
J1: ON
J1: ON
J1: OFF
Pos. right unit with
fresh air inlet in the
bottom
Pos. right unit with
fresh air inlet in the
top
Pos. left unit with
fresh air inlet in the
top
Pos. left unit with
fresh air inlet in the
bottom
Technical data
The control box has a built-in thermal fuse preventing an overload of the electronics.
A separate type G fuse must be installed to protect the main cable.
Controller inputs
Supply voltage:
50 – 60 Hz, 230 V AC +/- 15 %
Max. prefuse:
16 A
Voltage signal
0 – 10 V DC
Impedance (voltage signal)
10 kOhm
Serial communication
RS485 ABC-Bus
Rotation guard
Reed switch (also active in purging
operation)
Supply for Hall element
15 V DC
(internal pull-up 1.1 kOhm resistance)
Controller outputs
Relay output for alarm
NO relay 5 A, 250 V
LED indication
2-colour (green/red)
Torque
2 Nm, 4 Nm and 6 Nm
Enclosure IP54
Continued overleaf