Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: The CEFPLL10VDC (SEAL) should be installed to achieve
correct coverage of the area, see diagram B. Avoid locating this product
where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources.
3. To cover larger areas and corridors PIRs should be spaced in a 5 metre
grid formation, with one CEFPLL10VDC(SEAL) and the rest with switching
PIRs with Volt Free secondary output and Normally Closed, Logic Gold relay
contacts (CEFLPIRVFNCLG) with all Switch Line outputs wired in series
(diagram E).
4. Make sure the power is isolated from the circuit.
The PIR should be connected as shown in diagram C:
Thick wire
Thin wire
Brown
L
Live in
Red
+
1-10V control
Blue
N
Neutral in
Blue
-
0V reference
Start-up mode
When the PIR is powered up, it will switch on the load for 1 minute, the load
will then switch off and the PIR will enter its Operating Mode. If a manual
override-off switch is positioned before the PIR in the circuit (diagram C,
note 1) it will do this each time the wall switch is switched on. Alternatively,
if the wall switch is placed after the PIR (diagram C, note 2) it will not enter
the start-up mode each time.
Time, Lux and ‘Step Down’ set-up
For convenience, ensure that the TIME is set to the minimum when setting up
the LUX level. Afterwards set the TIME to a value suitable for the application.
The LUX is best set up when the local ambient light is at approximately
the minimum desired working light level. With the LUX set fully clockwise
wait for the PIR to switch off. Rotate the LUX adjuster slowly anticlockwise
(- to +), whilst waving your hand approximately 1m below the PIR, until the
load switches on.
The single adjuster spindle on the back of the PIR is used to regulate the ‘Step
Down’ illuminance function lux level, see diagram E opposite. This must be
adjusted in situ so that the desired level of brightness is achieved under the
luminaire(s) being controlled. In areas where no natural daylight is present it
is advised that the LUX level is set to
͚
. inhibit off.
Clearance hole
63 or 64mm (2.5") diameter
Springs can either be left closed (down
the side of the product) or opened out.
L
N
1
t
s
a
ll
a
b
10
1
t
s
a
ll
a
b
10
1
t
s
a
ll
a
b
10
CEFPLL10VDC(SEAL)
control lines
230 VAC
Optional
switch for
overriding off
TIME
min
max
20s
40s
1m15s
2m30s
5m
10m
10s
20m
40m
LUX
max
min
100
∞
1000
Typical settings
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
For optimum coverage
recommended mounting
height: 2.4 to 5m
A: Mounting diagram
B: Detection diagram
C: Wiring diagram, single PIR
D: Adjusting time and lux
at the side of product
‘Step Down’ set-up
The STEP DOWN low light level range is adjusted
via the spindle on the top of the product and allows
the 1-10VDC ballast to switch from 10% to 100% in
9 steps. Fully clockwise will allow the ballast to switch
to 100% on non-occupation. Fully anti-clockwise will
allow the ballast to switch to 10% on non-occupation.
E: ‘Step Down’ adjuster
at the top of the product
‘Step Down’
adjuster
100%
10%
Adjuster
guide
Switching Flex
Control
Flex