background image

SunCentric  Troubleshooting

–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Pump does not run (no shaft rotation)

– IF voltage at pump motor = 0 while voltage at power source is OK

Power circuit failure

Check the fuse or circuit breaker, see “Overload Protection”
Check the wires and connections
Check or bypass the float switch circuit, if there is one

– IF voltage at motor is normal

Motor brushes worn

Replace motor brushes

– IF voltage is very low or fuse blows or circuit breaker trips

Pump is jammed

See “Pump is jammed”, below

–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Pump turns but flow is less than normal

– IF system is solar-direct (no battery) and voltage at motor is below normal

PV (solar) array is undersized

See Minimum Array Size on the performance chart

PV array is wired wrong

Inspect, measure the voltage with pump disconnected (open circuit)
Open circuit voltage should be about 20V per “12V” increment

Array is positioned wrong
Partial shade or dirt on the PV array
Pump is partly jammed

See “Pump is jammed”, below

Undersized wire (see next line)

– IF system is battery OR solar-direct, and voltage at motor is below normal

Wire from power source to pump is undersized

With pump running, measure voltage at power source AND at motor
If difference (voltage drop) is greater than 3%, the wire is too small
(See “Wire Sizing”)

– IF voltage at motor is normal

Piping is undersized (See “Water Pipe Sizing Chart”)
Intake is restricted by debris
Outlet is restricted
Vertical lift is excessive
Pump is spinning in reverse

R and – wires

Impeller is clogged with debris
Air is trapped in a high spot in the pipe
Air is trapped in the pump

Rotate pump to one of the approved positions

Impeller is worn from abrasive silt

–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Pump does not stay primed

– IF it loses prime while the power is off

Foot valve is damaged

Replace foot valve

Содержание SunCentric Series

Страница 1: ...array tilts to follow the sun as it travels accross the sky Centrifugal pumps loose capacity quickly as solar intensity and motor speed decrease Therefore it is most economical to use a tracking array...

Страница 2: ...motive fuses are good for 24V nominal 30 Amp Max Paper cartridge type FRN R time delay fuses are available for 30 amp maximum and are rated to 120VDC A standard AC single phase fused disconnect switch...

Страница 3: ...watts A controller current booster is NOT required with SunCentric pumps Dankoff Solar Products Inc Ground the array framework to earth for lightning protection Do NOT ground the power negative pump...

Страница 4: ...foot valve must be used at the water intake to keep the pump primed Foot valves are available from any local pump supplier and from many hardware stores To prevent air from being drawn into suction p...

Страница 5: ...p of pump Air will be trapped at top of pump Water leak will damage motor Air will be trapped here NO Air will be trapped here NO INLET PIPE OUTLET PIPE YES NO IF water source is higher than the pump...

Страница 6: ...to stop the flow upon filling a tank However if the flow is 100 stopped there is danger that the water in the pump can get very hot from fluid friction and cause damage A float valve installation shou...

Страница 7: ...ge of water due to a worn shaft seal Be sure that this rubber slinger rotates with the motor shaft If it is cracked or if it does not turn with the shaft either replace it or glue it to the shaft coup...

Страница 8: ...ircuit voltage should be about 20V per 12V increment Array is positioned wrong Partial shade or dirt on the PV array Pump is partly jammed See Pump is jammed below Undersized wire see next line IF sys...

Страница 9: ...the pump s suction capacity This is called cavitation Lower the pump closer to the water source if possible Reduce friction in the intake pipe by using larger pipe and or eliminating sharp 90 degree e...

Страница 10: ...warranty Product liability except where mandated by law is limited to repair or replacement at the discretion of the manufacturer Manufacturer is not responsible for incidental or consequential damage...

Страница 11: ...73 2 61 1 34 0 46 0 18 0 07 2 0 7 6 10 6 3 16 1 64 0 55 0 21 0 08 0 02 2 2 8 3 13 3 3 79 1 96 0 67 0 25 0 09 0 03 2 4 9 1 14 9 4 44 2 31 0 79 0 30 0 11 0 04 2 6 9 9 5 15 2 66 0 90 0 35 0 14 0 05 2 8 1...

Отзывы: