Electrical data, connections and wiring
The CDS303 frequency converter generates by
design a compressor soft start with an default
initial ramp up of 2700rpm/s.
Current inrush will not exceed the frequency
converter maximum current.
Basically seen from the mains the inrush peak
reach a level which is only a few percent more
than the rated nominal current.
Soft-start control
Electrical power is connected to the compressor
terminals by Ø 4.8 mm (3/16") screws. The
maximum thightening torque is 3 Nm. Use a 1/4"
ring terminal on the power leads.
The cable gland has to be of EMC design to
garanty a good grounding of the armored cable.
Paint free areas on electrical box allow correct
ground continuity.
Electrical connections
The CDS303 frequency converter is preset to run
the VZH compressors clockwise so the only care
is to properly connect the CDS303 output to the
compressor connectors:
• CDS303 terminal U (96) to VZH terminal T1/U
• CDS303 terminal V (97) to VZH terminal T2/V
• CDS303 terminal W (98) to VZH terminal
T3/W
Mains connection to the CDS303 frequency
converter order has no influence on the output
phase sequence which is managed by the
frequency converter.
However, the connection between the drive and
the compressor can still be mis-wired. Special
attention needs to be paid and strictly follows
wire connection instruction.
The compressor terminal box IP rating according to CEI529 is IP54 when correctly sized IP54 rated
cable glands are used.
Motor protection is provided by the frequency
converter. All parameters are factory preset
in order to guaranty locked rotor or overload
current protection.
When a warning situation is reached in the
current control, the CDS303 frequency converter
will automatically reduce the compressor
speed in order to keep the motor current of the
compressor below the maximum allowed.
The maximum allowable voltage imbalance
between each phase is 3%. Voltage imbalance
causes high amperage over one or several
phases, which in turn leads to overheating and
possible drive damage.
Mains imbalance function in CDS303 frequency
converter can be set to “[0] Trip” or “[1] Warning”
in 14.12 parameter. It is, by default, factory preset
to “[1] Warning”.
Then the compressor electrical motor is never
affected by main voltage imbalance situations
which are totally made transparent by the
frequency converter.
Phase sequency and
reverse rotation
protection
IP rating
Motor protection
Voltage imbalance
Element
Numerals or letters
Meaning for the protection of equipment
First characteristic
numeral
0
1
2
3
4
5
6
Against ingress of solid foreign objects
(non protected)
≥ 50 mm diameter
≥ 12.6 mm diameter
≥ 2.5 mm diameter
≥ 1.0 mm diameter
dust protected
dust tight
Second
characteristic
numeral
0
1
2
3
4
5
6
7
8
Agains ingress of water with harmful effects
(non protected
vertically dripping
dripping (15° tilted)
spaying
splashing
jetting
porwerful jetting
temporary immersion
continuous immersion
39
FRCC.PC.023.A8.02
Application Guidelines