Application guidelines
36
FRCC.PC.023.A7.22
Single compressors
Electrical data, connections and wiring
Fuses / circuit breakers
Danfoss recommends using the fuses/circuit
breakers listed below to protect service
personnel and property in case of component
break-down in the frequency converter. For
circuit breakers, Moeller types have been tested
and are recommended. Other types of circuit
breakers may be used provided they limit the
energy to a level equal to or lower than the
Moeller types.
Frequency converter
EN50178
compliant fuses
UL Compliant fuses
Recommended circuit breaker
Bussmann
SIBA
Little fuse
IP20
IP55
Size
Type
Type RK1
Type J
Type T
Type RK1
Type RK1
Type RK1
Moeller type
200-240 V
CDS-15kW
125 A
gG
KTN-R125
JKS-150
JJN-125
2028220-125 KLN-R125
A2K-125R
NZMB1-A100
NZMB2-A200
CDS-18.5 kW
125 A
gG
KTN-R125
JKS-150
JJN-125
2028220-125 KLN-R125
A2K-125R
NZMB2-A200
NZMB2-A200
CDS-22 kW
160 A
gG
FWX-150
-
-
2028220-150 L25S-150
A25X-150
NZMB2-A200
NZMB2-A200
380-480 V
CDS-15 kW
63 A
gG
KTS-R50
JKS-50
JJS-50
5014006-050 KLS-R50
A6K-50R
PKZM4-50
PKZM4-63
CDS-18.5 Kw
63 A
gG
KTS-R60
JKS-60
JJS-60
5014006 -063 KLS-R60
A6K-60R
NZMB1-A100
NZMB1-A100
CDS-22 kW
80 A
gG
KTS-R80
JKS-80
JJS-80
2028220-100 KLS-R80
A6K-80R
NZMB1-A100
NZMB1-A100
525- 600V
CDS-18.5 kW
40A
gG
KTS-R50
JKS-50
JJS-50
5014006-050 KLS-R50
A6K-50R
NZMB1-A100
-
CDS-30 kW
63A
gG
KTS-R80
JKS-80
IJS-80
5014006-080 KLS-R80
A6K-80R
NZMB1-A100
-