3.7.7 5-6* Pulse Outputs
Parameters for configuring the scaling and output functions
of pulse outputs. The pulse outputs are designated to
terminals 27 or 29. Select terminal 27 output in
and terminal 29 output in
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Options for readout output variables:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop
[114]
Ext. Closed Loop
[115]
Ext. Closed Loop
Select the operation variable assigned for terminal 27
readouts.
This parameter cannot be adjusted while the motor is
running. Same options and functions as par. group 5-6*.
[0]
*
No operation
5-62 Pulse Output Max Freq #27
Set the maximum frequency for terminal 27, corresponding to the
output variable selected in
5-60 Terminal 27 Pulse Output Variable
.
This parameter cannot be adjusted while the motor is running.
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]
5-63 Terminal 29 Pulse Output Variable
Select the variable for viewing on the terminal 29 display.
This parameter cannot be adjusted while the motor is running.
Same options and functions as par. group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-65 Pulse Output Max Freq #29
Set the maximum frequency for terminal 29 corresponding to the
output variable set in
5-63 Terminal 29 Pulse Output Variable
This parameter cannot be adjusted while the motor is running.
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for read-out on terminal X30/6.
This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is installed
in the frequency converter.
Same options and functions as par. group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
Parameter Description
VLT
®
HVAC Drive Programming Guide
66
MG.11.CB.02 - VLT
®