16-71 Relay Output [bin]
Range:
Function:
0
*
[0 - 511 ]
View the settings of all relays.
R eadout choic e (P ar . 16-71):
R ela y output (bin):
OptionB car d r ela y 08
OptionB car d r ela y 07
P o w er car d r ela y 02
P o w er car d r ela y 01
OptionB car d r ela y 09
130BA195.10
0 0 0
0 0 bin
16-72 Counter A
Range:
Function:
0
*
[-2147483648 -
2147483647 ]
View the present value of Counter A.
Counters are useful as comparator
operands, see
.
The value can be reset or changed either
via digital inputs (parameter group 5-1*) or
by using an SLC action (
).
16-73 Counter B
Range:
Function:
0
*
[-2147483648 -
2147483647 ]
View the present value of Counter B.
Counters are useful as comparator
operands (
).
The value can be reset or changed either
via digital inputs (parameter group 5-1*) or
by using an SLC action (
).
16-75 Analog In X30/11
Range:
Function:
0.000
*
[-20.000 - 20.000 ] View the actual value at input X30/11
of MCB 101.
16-76 Analog In X30/12
Range:
Function:
0.000
*
[-20.000 - 20.000 ] View the actual value at input X30/12
of MCB 101.
16-77 Analog Out X30/8 [mA]
Range:
Function:
0.000
*
[0.000 - 30.000 ] View the actual value at input X30/8 in
mA.
3.16.6 16-8* Fieldbus & FC Port
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range:
Function:
0
*
[0 - 65535 ] View the two-byte Control word (CTW) received
from the Bus-Master. Interpretation of the
Control word depends on the fieldbus option
installed and the Control word profile selected
in
For more information please refer to the
relevant fieldbus manual.
16-82 Fieldbus REF 1
Range:
Function:
0
*
[-200 - 200 ] View the two-byte word sent with the control
word form the Bus-Master to set the reference
value.
For more information please refer to the
relevant fieldbus manual.
16-84 Comm. Option STW
Range:
Function:
0
*
[0 - 65535 ] View the extended fieldbus comm. option
status word.
For more information please refer to the
relevant fieldbus manual.
16-85 FC Port CTW 1
Range:
Function:
0
*
[0 - 65535 ] View the two-byte Control word (CTW) received
from the Bus-Master. Interpretation of the
control word depends on the fieldbus option
installed and the Control word profile selected
in
16-86 FC Port REF 1
Range:
Function:
0
*
[-200 - 200 ] View the two-byte Status word (STW) sent to
the Bus-Master. Interpretation of the Status
word depends on the fieldbus option installed
and the Control word profile selected in
.
3.16.7 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
Parameter Description
VLT
®
HVAC Drive Programming Guide
118
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3