8-05 End-of-Timeout Function
Option:
Function:
[1]
*
Resume set-
up
Resumes the set-up active prior to the time-
out.
8-06 Reset Control Timeout
Option:
Function:
This parameter is active only when the choice
Hold
set-up
[0] has been selected in
.
[0]
*
Do not
reset
Retains the set-up specified in
, [Select setup 1-4] following a control
time-out.
[1]
Do reset Returns the frequency converter to the original
set-up following a control word time-out. When
the value is set to
Do reset
[1], the frequency
converter performs the reset and then
immediately reverts to the
Do not reset
[0] setting.
8-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for
BACnet.
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Option:
Function:
Select the interpretation of the control
and status words corresponding to the
installed fieldbus. Only the selections
valid for the fieldbus installed in slot A
will be visible in the LCP display.
[0]
*
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of
bits 12 – 15 in the status word.
[0]
No function
The input is always low.
[1]
*
Profile Default
Depended on the profile set in
.
[2]
Alarm 68 Only
The input will go high whenever Alarm 68
is active and will go low whenever no
alarm 68 is active
[3]
Trip excl Alarm
68
The input will go high whenever Trip on
other Alarms then Alarm 68 is active.
8-13 Configurable Status Word STW
Option:
Function:
[10] T18 DI status.
The input will go high whenever T18 has
24V and will go low whenever T18 has 0V
[11] T19 DI status.
The input will go high whenever T19 has
24V and will go low whenever T19 has 0V
[12] T27 DI status.
The input will go high whenever T27 has
24V and will go low whenever T27 has 0V
[13] T29 DI status.
The input will go high whenever T29 has
24V and will go low whenever T29 has 0V
[14] T32 DI status.
The input will go high whenever T32 has
24V and will go low whenever T32 has 0V
[15] T33 DI status.
The input will go high whenever T33 has
24V and will go low whenever T33 has 0V
[16] T37 DI status
The input will go high whenever T37 has
0V and will go low whenever T37 has 24V
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor..
[30] Brake fault
(IGBT)
Will go high when the brake IGBT is short-
circuited.
[40] Out of ref range If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[60] Comparator 0
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[61] Comparator 1
If Comparator 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[62] Comparator 2
If Comparator 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[63] Comparator 3
If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[64] Comparator 4
If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[65] Comparator 5
If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[70] Logic Rule 0
If Logic Rule 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[71] Logic Rule 1
If Logic Rule 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[72] Logic Rule 2
If Logic Rule 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[73] Logic Rule 3
If Logic Rule 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[74] Logic Rule 4
If Logic Rule 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[75] Logic Rule 5
If Logic Rule 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[80] SL Digital
Output A
SL Controller Action. The input will go high
whenever the Smart Logic Action [38] Set
dig. out. A high is executed. The input will
go low whenever the Smart Logic Action
[32] Set dig. out. A low is executed.
[81] SL Digital
Output B
SL Controller Action. The input will go high
whenever the Smart Logic Action [39] Set
dig. out. A high is executed. The input will
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
75