manualshive.com logo in svg
background image

Danfoss Drives

, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80, www.danfoss.com/drives • E-mail: [email protected]

 

MF004A02 

VLT® is a trademark of Danfoss A/S 

Produced by KKM 2007.10

Programming for No-Flow detection 
is simplified with a number of para- 
meters that are pre-programmed into 

the drive. Prior to programming this 
feature, commission the drive by 
using the parameters in the Quick 

Menu Q2 Quick Set-Up. Then perform 
the following steps for programming 

No-Flow detection:

Par.#

Description

Settings

Comments

Factory 

setting

Recommended 

setting

22-20

Low Power Auto Set-up Disable

Enable

Close the outlet valve for the pump before starting Auto Set-up.  Select Enable 

and follow the instruction on the LCP.  After Auto Set-up is complete, open the 

pump outlet valve.

The following parameters are accessed through the Main Menu and will be stored after pressing the [OK] key to save the results after the auto-tuning
22-33

Low Speed  

[Hz]

When Low Power Auto Set-up is used, 50% of the drive’s maximum frequency 

will be stored here. This can be manually edited, if desired.

22-34

Low Speed Power [kW]

When Low Power Auto Set-up is used, the output power measured under 

no-flow conditions at 50% speed will be stored here. This can be manually 

edited, if desired.

22-37

High Speed  

[Hz]

When Low Power Auto Set-up is used, 85% of the drive’s maximum frequency 

will be stored here. This can be manually edited, if desired.

22-3

High Speed Power [kW]

When Low Power Auto Set-up is used, the output power measured under 

no-flow conditions at 85% speed will be stored here. This can be manually 

edited, if desired.

These parameters are used after Auto Set-up and the No-Flow feature is operating
22 - 30

No-Flow Power

When the drive is running, this parameter will show the power level that will 

be interpreted as producing no flow at the current motor speed. 

22 - 31

Power Correction 

Factor

100%

110%

This parameter is used to raise or lower the no-flow power curve to the 

percentage entered here. Values above 100% help ensure the drive reliably 

detects no-flow.

The following parameters determine the action that the drive will take if a no flow condition is detected
22-21

Low Power  

Detection

Disable

Enable

To activate no-flow based on power

22-23

No-Flow Function

Off

Sleep Mode/

Warning/Alarm

Select action 

22-24

No-Flow Delay

10 sec.

Set the time delay before the drive will perform the No-Flow Function.  

Generally set longer than the decel ramp time.

The following parameters give and indication to a BMS if a no flow condition is detected

5-40

Function Relay 

[190] No-Flow

Program one of the relays to selection [190], No-Flow.  The selected relay will 

be activated when No-Flow occurs.

Digital Output

[190] No-Flow

A digital output can be used to indicate a no flow condition.  Use the 

parameter that sets the function of the desired digital output.

The following are used if No-Flow is reported via serial communications

Protocol

Warning Word

BACnet

BV:77 No Flow

LonWorks

nvoWarningword Bit 37

Modbus RTU 

TU

Register 16930 Bit 6 = 1

Programming No-Flow detection

Отзывы: