7.1.3 Status Information (Assembly Instance 154d)
To retrieve status data from the soft starter, use assembly class 04d (0x04), assembly instance 154d (0x9A), attribute 03d (0x03).
7.1.3.1 Bytes 0–1: Starter State
Bits
Function
Details
0
Ready
0 = Not ready
1 = Ready to start
1
Operating mode
0 = Program mode
1 = Operating mode
2
Running
0 = Not ready, ready to start, or tripped
1 = Starting, Running, Stopping, or Jogging
3
Trip
0 = Not tripped
1 = Tripped
4
Jog forward
1 = Jog forward
5
Jog reverse
1 = Jog reverse
6
Reserved
7
Warning
0 = No warning
1 = Warning
8
Ramping
1 = Running (full voltage at the motor)
9
Command source
0 = Remote LCP, digital input, clock
1 = Network
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Temperature limit
0 = Motor operating within thermal capacity (thermal model)
1 = Motor operating above thermal capacity (thermal model)
7.1.3.2 Bytes 2–3: Reserved
Bits
Function
Details
0–15
Reserved
7.1.3.3 Bytes 4–7: Motor Current
Bits
Function
Details
0–31 Motor current Average rms current across all 3 phases. Measured current is shown as a 32-bit value to 2 decimal places.
10d (0x0A) = 0.10 A
3450d (0xD7A) = 34.50 A
AN353423548483en-000101 / 130R0945 | 19
Danfoss A/S © 2020.12
Messaging
EtherNet/IP Card
Installation Guide