1-40 Back EMF at 1000 RPM
Range:
Function:
measured between 2 lines. If the value is
not available for a motor speed of 1000
RPM, calculate the correct value as follows:
If back EMF is, for example, 320 V at 1800
RPM, it can be calculated at 1000 RPM:
Example
Back EMF 320 V at 1800 RPM. Back EMF =
(Voltage/RPM)*1000 = (320/1800)*1000 =
178.
This parameter is only active when
parameter 1-10 Motor Construction
is set to
options that enable PM (permanent
magnet) motors.
NOTICE
When using PM motors, it is
recommended to use brake resistors.
1-42 Motor Cable Length
Range:
Function:
50 m
*
[0 - 100 m]
Set the motor cable length in meters.
1-43 Motor Cable Length Feet
Range:
Function:
164 ft
*
[0 - 328 ft] Set the motor cable length. The length unit
is foot.
1-44 d-axis Inductance Sat. (LdSat)
Range:
Function:
Size
related
[ 0 -
1000
mH]
This parameter is active only when
parameter 1-10 Motor Construction
is set to
[3]
PM, salient IPM, Sat
.
This parameter corresponds to the saturation
inductance of d-axis. The default value is the
value set in
parameter 1-37 d-axis Inductance
. In most cases, do not change the default
value. If the motor supplier provides the
saturation curve, enter the d-axis inductance
value, which is 100% of the nominal current.
1-45 q-axis Inductance Sat. (LqSat)
Range:
Function:
Size
related
*
[ 0 -
1000
mH]
This parameter is active only when
parameter 1-10 Motor Construction
is set to
[3] PM, salient IPM, Sat
.
This parameter corresponds to the q-axis
saturation inductance. The default value is
the value set in
. In most cases, do not
change the default value. If the motor
supplier provides the saturation curve, enter
1-45 q-axis Inductance Sat. (LqSat)
Range:
Function:
the q-axis inductance value, which is 100%
of the nominal current.
1-46 Position Detection Gain
Range:
Function:
100 %
*
[ 20 -
200 %]
Adjusts the amplitude of the test pulse
during position detection at start. Adjust
this parameter to improve the position
measurement.
1-48 Current at Min Inductance for d-axis
Range:
Function:
100 % [ 20 - 200 %] Use this parameter to set the inductance
saturation point.
1-49 Current at Min Inductance for q-axis
Range:
Function:
100 % [ 20 -
200 %]
This parameter specifies the saturation curve of
the q-inductance values. From 20–100% of this
parameter, the inductance is linearly
approximated due to
and
. These parameters are
related to the motor nameplate load compen-
sations, the application load type, and the
electronic brake function for quick stop/hold of
the motor.
1-50 Motor Magnetisation at Zero Speed
Range:
Function:
100
%
*
[0 -
300 %
]
Use this parameter along with
parameter 1-52 Min
Speed Normal Magnetising [Hz]
to obtain a
different thermal load on the motor when running
at low speed.
Enter a value that is a percentage of the rated
magnetizing current. If the setting is too low, the
torque on the motor shaft may be reduced.
Magn. current
130BB780.10
Hz
Par.1-50
90%
Par.1-52
Illustration 4.1 Motor Magnetization
1-52 Min Speed Normal Magnetising [Hz]
Range:
Function:
1 Hz
*
[ 0.1 - 10.0
Hz]
Set the required frequency for normal
magnetizing current. Use this parameter
along with
, also see
.
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
35
4
4
Содержание VLT Midi Drive FC 280
Страница 1: ...Programming Guide VLT Midi Drive FC 280 vlt drives danfoss com ...
Страница 2: ......
Страница 143: ...Index Programming Guide MG07C102 Danfoss A S 12 2015 All rights reserved 141 ...