e30bv051.10
VLT
MADE IN
DENMARK
T/C: FC-280PK37T4E20H1BXCXXXSXXXXAX
0.37kW 0.5HP
IN: 3x380-480V 50/60Hz, 1.2/1.0A
OUT: 3x0-Vin 0-500Hz, 1.2/1.1A
IP20
P/N: 134U2184 S/N: 000000G000
Midi Drive
www.danfoss.com
CAUTION / ATTENTION:
WARNING / AVERTISSEMENT:
See manual for special condition/mains fuse
Voir manual de conditions speciales/fusibles
Enclosure: See manual
5AF3 E358502 IND.CONT.EQ.
Stored charge, wait 4 min.
Charge résiduelle, attendez 4 min.
1
2
3
4
6
5
R
US LISTED
www.tuv.com
ID 0600000000
Danfoss A/S, 6430 Nordborg, Denmark
1
Type code
2
Ordering number
3
Power rating
4
Input voltage, frequency, and current (at low/high
voltages)
5
Output voltage, frequency, and current (at low/high
voltages)
6
Enclosure protection rating
1.6 EMC-compliant Installation
For more information, refer to the VLT
®
Midi Drive FC 280 Operating Guide.
Use shielded cables for motor (unshielded cables in metal conduit are acceptable), brake, DC, and control wiring.
Ensure that motor, brake, and DC cables are as short as possible to reduce the interference level from the entire system. Provide
a minimum space of 200 mm (7.9 in) between mains input, motor cables, and control cables.
Convey the currents back to the drive using a metal mounting plate. Ensure good electrical contact from the mounting plate
through the mounting screws to the metal frame of the enclosure.
If the shield connection points have a voltage potential difference, connect a low impedance equalizing wire parallel to the
shielded cable.
When using relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the
ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current
loops.
1.7 Power Ratings
There are 3 voltage ranges for FC 280:
1-phase 200–240 V
3-phase 200–240 V
3-phase 380–480 V
Table 1: Enclosure Sizes and Power Ratings
Enclo-
sure
size
K1
K2
K3
K4
K5
Power
size
1-phase
200–240
V
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5 (2.0)
2.2 (3.0)
–
–
–
AN41533976851001-000101 /
130R1264
6
| Danfoss A/S © 2022.06
VLT® Midi Drive FC 280
English